Operation
P54x/EN OP/La4
MiCOM P543, P544, P545 & P546
(OP) 5-117
OP
5. If no messages arrive from either end then after one second the relay will change to the
configuration that was last selected, i.e. the configuration before power down. Once
messages begin to arrive again, the relay will check them for validity against the current
scheme. If one relay is 3-ended and the other is 2-ended then the configuration will
change to 2-ended. If both are 3-ended or the same 2-ended scheme then that will
become the configuration. If two relays have different 2-ended configurations then they
are unable to determine which one to use and will each generate a configuration error
alarm and each relay will remain in its current configuration. This condition can be
cleared by restoring the relays or by removing the supply to the relay with the incorrect
configuration.
6. If all the relays in a scheme are energized simultaneously then the configuration will
revert to 3-ended if all the communication channels are healthy. This occurs because all
the relays are waiting to be told their configuration and all default to 3-ended. This is a
very unlikely event in normal use.
7. In cases where a communication channel has only half failed i.e. the receive channel
has failed but not the transmit channel, then there may be configuration errors on power
up due to the fact that the relays are not communicating correctly. If the status is
available via the third relay and healthy communications via its two channels then the
scheme will stabilize correctly.
2.2
InterMiCOM
64
introduction
Eight digital signals from local relay to the remote relay can be sent by using Programmable
InterMiCOM
64
(IM64) teleprotection available in MiCOM P54x. This teleprotection uses the
protection communication channel described in section 2.1.
In this scheme the signaling channel is used to convey simple ON/OFF data (from a local
protection device) thereby providing some additional information to a remote device which
can be used to accelerate in-zone fault clearance and/or prevent out-of-zone tripping.
2.2.1
Definition of teleprotection commands
The decision to send a command is made by a local protective relay operation, and three
generic types of signal are available:
Intertripping
In intertripping (direct or transfer tripping applications), the command is not supervised at the
receiving end by any protection relay and simply causes CB operation. Since no checking of
the received signal by another protection device is performed, it is absolutely essential that
any noise on the signaling channel isn’t seen as being a valid signal. In other words, an
intertripping channel must be very secure.
Permissive
In permissive applications, tripping is only permitted when the command coincides with a
protection operation at the receiving end. Since this applies a second, independent check
before tripping, the signaling channel for permissive schemes do not have to be as secure as
for intertripping channels.
Blocking
In blocking applications, tripping is only permitted when no signal is received but a protection
operation has occurred. In other words, when a command is transmitted, the receiving end
device is blocked from operating even if a protection operation occurs. Since the signal is
used to prevent tripping, it is imperative that a signal is received whenever possible and as
quickly as possible. In other words, a blocking channel must be fast and dependable.
The requirements for the three channel types are represented pictorially in Figure 76.
Содержание MiCOM P54 Series
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P54x EN SS H11 SS SAFETY SECTION...
Страница 6: ...P54x EN SS H11 Safety Section SS...
Страница 8: ...P54x EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P54x EN IT La4 Introduction MiCOM P543 P544 P545 P546 IT...
Страница 18: ...P54x EN IT La4 Introduction IT 1 2 MiCOM P543 P544 P545 P546 IT...
Страница 28: ...P54x EN IT La4 Introduction IT 1 12 MiCOM P543 P544 P545 P546 IT...
Страница 30: ...P54x EN TD La4 Technical Data MiCOM P543 P544 P545 P546 TD...
Страница 58: ...P54x EN GS La4 Getting Started MiCOM P543 P544 P545 P546 GS...
Страница 78: ...P54x EN ST La4 Settings MiCOM P543 P544 P545 P546 ST...
Страница 172: ...P54x EN ST La4 Settings ST 4 94 MiCOM P543 P544 P545 P546 ST...
Страница 174: ...P54x EN OP La4 Operation MiCOM P543 P544 P545 P546 OP...
Страница 362: ...P54x EN OP La4 Operation OP 5 188 MiCOM P543 P544 P545 P546 OP Figure 118 Auto relose timing diagram leader follower 1ph...
Страница 432: ...P54x EN OP B94 Operation OP 5 260 MiCOM P543 P544 P545 P546 OP Figure 61 CB2 synch check signals...
Страница 442: ...P54x EN OP B94 Operation OP 5 270 MiCOM P543 P544 P545 P546 OP...
Страница 444: ...P54x EN AP La4 Application Notes MiCOM P543 P544 P545 P546 AP...
Страница 534: ...P54x EN PL La4 Programmable Logic MiCOM P543 P544 P545 P546 PL...
Страница 538: ...P54x EN PL La4 Programmable Logic PL 7 4 MiCOM P543 P544 P545 P546 PL...
Страница 602: ...P54x EN PL La4 Programmable Logic PL 7 68 MiCOM P543 P544 P545 P546 Output Contacts PL...
Страница 603: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 69 Output Contacts PL...
Страница 606: ...P54x EN PL La4 Programmable Logic PL 7 72 MiCOM P543 P544 P545 P546 PL...
Страница 616: ...P54x EN PL La4 Programmable Logic PL 7 82 MiCOM P543 P544 P545 P546 Output Contacts PL...
Страница 619: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 85 PL...
Страница 620: ...P54x EN PL La4 Programmable Logic PL 7 86 MiCOM P543 P544 P545 P546 PL...
Страница 621: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 87 PL...
Страница 624: ...P54x EN PL La4 Programmable Logic PL 7 90 MiCOM P543 P544 P545 P546 PL...
Страница 629: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 95 Output Contacts PL...
Страница 630: ...P54x EN PL La4 Programmable Logic PL 7 96 MiCOM P543 P544 P545 P546 PL...
Страница 631: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 97 PL...
Страница 633: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 99 PL...
Страница 637: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 103 PL...
Страница 641: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 107 Output Contacts PL...
Страница 642: ...P54x EN PL La4 Programmable Logic PL 7 108 MiCOM P543 P544 P545 P546 Output Contacts PL...
Страница 643: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 109 LEDs PL...
Страница 644: ...P54x EN PL La4 Programmable Logic PL 7 110 MiCOM P543 P544 P545 P546 PL...
Страница 645: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 111 PL...
Страница 647: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 113 PL...
Страница 653: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 119 Output Contacts PL...
Страница 655: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 121 Output Contacts PL...
Страница 656: ...P54x EN PL La4 Programmable Logic PL 7 122 MiCOM P543 P544 P545 P546 LEDs PL...
Страница 663: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 129 PL...
Страница 667: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 133 Output Contacts PL...
Страница 669: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 135 Output Contacts PL...
Страница 671: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 137 PL...
Страница 672: ...P54x EN PL La4 Programmable Logic PL 7 138 MiCOM P543 P544 P545 P546 PL...
Страница 676: ...P54x EN PL La4 Programmable Logic PL 7 142 MiCOM P543 P544 P545 P546 PL...
Страница 681: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 147 Output Contacts PL...
Страница 688: ...P54x EN PL La4 Programmable Logic PL 7 154 MiCOM P543 P544 P545 P546 PL...
Страница 689: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 155 PL...
Страница 690: ...P54x EN PL La4 Programmable Logic PL 7 156 MiCOM P543 P544 P545 P546 PL...
Страница 696: ...P54x EN PL La4 Programmable Logic PL 7 162 MiCOM P543 P544 P545 P546 Output Contacts PL...
Страница 698: ...P54x EN PL La4 Programmable Logic PL 7 164 MiCOM P543 P544 P545 P546 PL...
Страница 701: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 167 PL...
Страница 703: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 169 PL...
Страница 704: ...P54x EN PL La4 Programmable Logic PL 7 170 MiCOM P543 P544 P545 P546 PL...
Страница 705: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 171 PL...
Страница 706: ...P54x EN PL La4 Programmable Logic PL 7 172 MiCOM P543 P544 P545 P546 LEDs PL...
Страница 708: ...P54x EN MR La4 Measurements and Recording MiCOM P543 P544 P545 P546 MR...
Страница 710: ...P54x EN MR La4 Measurements and Recording MR 8 2 MiCOM P543 P544 P545 P546 MR...
Страница 726: ...P54x EN FD La4 Firmware Design MiCOM P543 P544 P545 P546 FD...
Страница 748: ...P54x EN CM La4 Commissioning MiCOM P543 P544 P545 P546 CM...
Страница 754: ...P54x EN CM La4 Commissioning CM 10 6 MiCOM P543 P544 P545 P546 CM...
Страница 832: ...P54x EN CM La4 Commissioning CM 10 84 MiCOM P543 P544 P545 P546 CM Commissioning Engineer Customer Witness Date Date...
Страница 874: ...P54x EN MT La4 Maintenance MiCOM P543 P544 P545 P546 MT MT...
Страница 876: ...P54x EN MT La4 Maintenance MT 11 2 MiCOM P543 P544 P545 P546 MT...
Страница 882: ...P54x EN TS La4 Troubleshooting MiCOM P543 P544 P545 P546 TS...
Страница 884: ...P54x EN TS La4 Troubleshooting TS 12 2 MiCOM P543 P544 P545 P546 TS...
Страница 894: ...P54x EN SC La4 SCADA Communications MiCOM P543 P544 P545 P546 SC...
Страница 928: ...P54x EN SG La4 Symbols and Glossary MiCOM P543 P544 P545 P546 SG...
Страница 938: ...P54x EN SG La4 Symbols and Glossary SG 14 10 MiCOM P543 P544 P545 P546 SG...
Страница 940: ...P54x EN IN La4 Installation MiCOM P543 P544 P545 P546 IN...
Страница 947: ...Installation P54x EN IN La4 MiCOM P543 P544 P545 P546 IN 15 7 IN P0147ENd Figure 2 Rack mounting of panel mount relays...
Страница 957: ...Installation P54x EN IN La4 MiCOM P543 P544 P545 P546 IN 15 17 IN 10P54400_1 Figure 10 P544 external connection diagram...
Страница 966: ...P54x EN IN La4 Installation IN 15 26 MiCOM P543 P544 P545 P546 IN Figure 19 P546 external connection diagram...
Страница 973: ...Installation P54x EN IN La4 MiCOM P543 P544 P545 P546 IN 15 33 IN Figure 26 P546 Final assembly drawing...
Страница 974: ...P54x EN IN La4 Installation IN 15 34 MiCOM P543 P544 P545 P546 IN...
Страница 976: ...P54x EN VH La4 Firmware and Service Manual Version History MiCOM P543 P544 P545 P546 VH...
Страница 1023: ......