M3x5/EN M/B
User Manual
Page 34
iSTAT M3x5
When entering the installation wizard the following display is shown:
Installation
Welcome to the
Installation Wizard.
Press OK to continue.
Main menu
The Wizard then routes the user through the following screens.
Language
Set device language.
Date
Set device date.
Time
Set device time. If instrument is connected to one of supported time synchronisation
sources, date and time are automatically set.
Connection mode
Choose connection from a list of supported connection modes.
Primary voltage
Set primary voltage of monitored system if a device is connected indirectly by means of a
voltage transformer. If device is connected directly to a low voltage enter this value.
Secondary voltage
Set secondary voltage if a voltage transformer is used; set voltage of low voltage network if
connection is direct.
Primary current
Set primary current of monitored system if a device is connected indirectly by means of a
current transformer. Otherwise primary and secondary current should remain the same.
Secondary current
Set secondary current of current transformer or the value of nominal current if connection is
direct.
Common energy counter resolution
Define Common energy counter resolution as recommended in table below, where Individual
counter resolution is at default value 10. Values of primary voltage and current determine
proper Common energy counter resolution. For detailed information about setting energy
parameters see section 10.9.