21.3 100% VALUE CALCULATIONS
Un = (R40147 / R40146) * R30015 * R40149
In =
(R40145 / R40144) * R30017 * R40148
Pn = Un*In
It =
In ; for Connection Mode: 1b
It =
3*In ; for Connection Modes: 3b, 4b, 3u, 4u
Pt =
Pn ; for Connection Mode: 1b
Pt =
3*Pn ; for Connection Modes: 3b, 4b, 3u, 4u
Fn = R40150
Register Content
30015 Calibration
voltage
30017 Calibration
current
Register Content
Data Ind Values /
Dependencies
Min Max
P.
Level
40143 Connection
Mode
T1 0 No
mode
1 5
2
1
1b - Single Phase
2
3b - 3 phase 3 wire
balanced
3
4b - 3 phase 4 wire
balanced
4
3u - 3 phase 3 wire
unbalanced
5
4u - 3 phase 4 wire
unbalanced
40144 CT
Secondary
T4 mA
2
40145 CT
Primary T4 A/10
2
40146 VT
Secondary
T4 mV
2
40147 VT
Primary T4 V/10
2
40148 Current
input
range (%)
T16
10000 for 100%
5,00 200,00 2
40149 Voltage
input
range (%)
T16
10000 for 100%
2,50 100,00 2
40150 Frequency
nominal value
T1 Hz
10 1000 2