INTERNET
– option that is available on request. It allows to connect the controller to the network by ethernet cable or WiFi.
With the browser one can observe and change some parameters.
•
UTP cable type connection
o
Mode :
OFF
or
ON
– turning off or on the ethernet communication module
o
Password:
…………….
– six-letter password is necessary to run the application in the browser for ex. "
sekret
"
o
WWW address:
- - -, - - -, - - -, - - -
your local IP address which is set in your home router for the controller
for ex.
192.168.1.154
•
WiFi type connection
o
Mode :
OFF
, ON
or
SEARCH
– in 'search' mode you can find name of the network (SSID). To narrow the
search enter the first letter or set question mark ? to find all.
o
SSID WiFi : "name of your network". Can be entered or changed in search mode. To finish entering SSID name
you have to choose the "green square" as a mark.
o
Passw WiFi : "password of your network" Entering marks is the same as above.
o
IP address :
- - -, - - -, - - -, - - -
your local IP address which is set in your home router for the controller
for ex.
192.168.1.123
o
Passw WWW: . . . . . . . . . . . – six-letter password is necessary to run the application in the browser
for ex. "
sekret"
Starting up the web-browser is to write down the IP address with the password for ex. like in fig. below
192.168.1.154/sekret/
If it's done well – so it is configured correctly there is following application window on the screen of the computer:
MODBUS TCP
– option that is available on request. It allows to connect the controller to the BMS network by WiFi. To set or
read parameters controller use 0x03=Read Holding Register, 0x06=Write Single Register and 0x10=Write Multiple Registers
•
WiFi type connection
o
Mode, SSID WiFi, Passw WiFi and IP address are the same as above in Internet configuration.
o
Slave ID: ………… - its slave address (number) of your controller in modbus network.
5.
Alarm and information messages
The display has got a special field (next to data and time) where there is shown the information or alarm messages.
FILTERS INSPECT.
– this message is displayed every 6 months. This information will be cancelled after pressing icon,
confirming message receipt.
CONNECT. ERROR
– this is high level alarm message, informing us that the control panel (display TFT) can not be connected
to the relay module. Possible reason are:
- the communication wire can be damaged
- improper connection in the relay or TFT panel
- damage of relay panel's controller
SENSOR ERROR
- the system signals the temperature sensor's damage. According which sensor is out of order the
sign
ERROR
should appear on the place where normally temperature data are displayed. If there are
more broken sensors, the other signs are to be displayed simultaneously.
PRESSOST. ERROR
- if the controller is configured to co-work with pressostat in frost protection and system detects the signal
in spite of the fact that temperature is above 0°C (no possibility frosting) so that situation can occur when
pressostat is damage or exchanger is dirty. One is obligated to control the pressostat and condition of
exchanger.