AIR DISTRIB.

 – [they are a active only for EC fans] Difference between intake air and extract air creates high pressure or 

underpressure in rooms. Generally installation supplying the air from the external inlet has got different resistances than power 
installation of exchanger GHE. So that it is possible to correct the pressure for the external inlet and exchanger GHE in the 
controller. To do some corrections in external input probe one should turn off the GHE at first. Later go to the "CORRECT.." option. 
In window the high pressure sign 

pout 

 should be visible. It means that correction is related to external input. In the right column 

there are particular rotation's deviation from the nominal value, measured in [%]. Positive values stands for work with high pressure 
and negative ones the underpressure. The values of all corrections can be changed in range of -10% ÷ +25%. During the correction 
controller automatically change the gears matching them to the current corrected value allowing to current pressure measurement. 
Correction for GHE is made in same way. One has got to the GHE setting and set it for ON. Again, one need to go back to the 
CORRECT… option Now in the window there is visible the following sign

 

pghe

  - standing for the GHE mode of correction. Edition 

is the same as above. 
 
 

 

MOTORS

 – type of the motors, which are mounted in recuperator. Option available: 

 

 

 

Type : 

AC

 

- motors powered by 230VAC 

 

Type : 

EC

 

- motors powered by 230VAC but controlled by 0÷10VDC signal 

 

Speed number

 :

 [

1÷5

] – number of speeds (gears) For EC fans it can be taken 5 value and for AC fans it depends on 

their construction. 

 
 
 

 

DEFROST

 – configuration procedures for protection against freezing of the heat exchanger. 

 

 

 

Mode: 

OFF

 – the procedure is totally off and system doesn't react for any signal. This solution can be use in case that 

the recuperator is provided with internal defrosting system, for ex. supply air ventilator is powered by pressostat switch 
or when the manufacturer of recuperator gives a guarantee that this doesn't frost. 

 

Tout <

 [-1° to -15°C] – Below that temperature the frost process can occur 

 

Preheater P/N

  

[-3° to -7°C] – the temperature of operating the preheater as a frost protection. Relay connector 

marked (

A-B

) can be used to direct switching of preheater. The maximum power that can be connected directly 

cannot exeed 0.8kW. In case of bigger power you should use external relay. For such a operation one need to choose  

Preheater P …. 

(active relay turn the heater on) In case of using the heater with thiristor / triack controller for. ex. 

ENO.T one need  to select the 

Preheater N …. 

(active relay turn the heater off)  

For measurment of the air temperature behind the preheater we use GHE sensor (

Tg

). 

 
 
 
 

 

BACKLIGHT

 –  controller is provided with backlight display LCD. The intensity can be set by user.  

 

 

 

Config : 

CONST

 or 

AUTO

 – in AUTO option after turning the backlight off the short pressing screen / touch pad 

causes its rebooting. 

 

Level: 

[0 ÷ 100%]

 – the value of backlight intensity 

 
 
 
 

 

HEATER

 – the controller can drive heater using 0-10VDC signal with PI algorithm. 

 

 

 

Config : 

OFF

 

or

 

HE

 

or 

HW

 

 – it can be selected what type of the heater (electric HE or water HW) has to operated by 

controller. In case of water heater the frost protection procedure can open valve totally. To input WE5 one needs to 
connect the thermostat's connectors protecting the heater. 

>> Controller settings PI <<

 

 

Kp – 

[1÷100%]

  its a gain factor of the proportional part 

 

Ti – 

[10÷990s]

  its a integration time 

 

TU: 

[15 ÷ 50°C]

 the temperature which should be maintained by heater Sensor 

Ts

 (supply air) should be installed 

behind the heater 

 
 
 
 
 
 
 
 
 
 

Содержание MSR-20

Страница 1: ...set of rotation 2 in english ver icon name is rot shortphrase of rotation displaying the shortened information about current configurations sets 3 switching to controller s configuration mode 4 2 Manu...

Страница 2: ...e following functions escape the same function as the Esc computer button the minus value decreasing the value of the edited parameter the plus value increasing the value of the edited parameter appro...

Страница 3: ...to normal operation If you press the switch again during this operation it will cause the break of the procedure and earlier return to normal mode mode 3 Fire protection fan SUPL STOP fan EXH MAX This...

Страница 4: ...eat exchanger Mode OFF the procedure is totally off and system doesn t react for any signal This solution can be use in case that the recuperator is provided with internal defrosting system for ex sup...

Страница 5: ...request It allows to connect the controller to the BMS network by WiFi To set or read parameters controller use 0x03 Read Holding Register 0x06 Write Single Register and 0x10 Write Multiple Registers...

Страница 6: ...nnect gently upper and lower half b The relay module Installation and wiring must be carried out with power off Diagrams are supplied separately The module should be mounted in a recuperator or as clo...

Страница 7: ...ller can be received by the customer or sent to the client without the cost of transport service will repair it within 14 working days this period may be extended with the time that is taken to bring...

Отзывы: