NLLW 50 

– ‚User guide

 

20 

Failure calling is not repeated. It means that all numbers are calling only 

once  And  then  NLLW  hang  up.  Further  round  might  be  activated  only  by  new 
change on input INPUT. The voltage must returns back to stand by mode. The 
change on input INPUT must happen again. During failure calling are all other 
features available.  

During  failure  calling  is  not  lighting  any  indicator.  It  is  not  voice 

communication. The call is generating beeps 

– via. Table 1 page. 18.  

2.2.3 Calling from  INPUT  - Technical call 

 

Calling from activated input INPUT is named technical calling - set 

parameter 

390

. This call is acoustic - possible talking and indication LEDs is 

like as Emergency call. Telephone number and other features is same like as 
failure call. 

2.2.4 Service calling ( from timer) 

Service calling is optional parameter

. You alsé define if this parameter is 

activated since first connection of NLLW to telephone line.This service calling is 
adjustable from 1 to 9 day period, for example 3 means that NLLW is make 
automatically every 3th day a call to preprogrammed number. (test of NLLW  
functionality). 

For  service  calling  you  programm  special  number  which  might  be  of 

course the same as emergency or failure calling number. You can also select if 
will be dialling only this number or all round of emergeny  numbers ( then you 
have max 7 numbers) .   

The  service  calling  is  repeated  in  period  0-9  min  (  programmable)  until 

succesfull  call  (  confirmation).  The  repeated  time  between  calls  is 
programmable  because  to  service  department  can  call  more  NLLW.  To  avoid 
of  problem  that  service  department  line  is  busy  you  can  programm  different 
time period for service calling up installation place. 

During  failure  calling  is  not  lighting  any  indicator.  It  is  not  voice 

communication. The call is generating beeps 

– via. Table 1 page. 18.  

2.2.5 End of calling 

– call confirmation 

The  NLLW  enables  to  programm  at  every  number  if  will  be  confirm  or 

not.  Every call needs authorisation if it was succesfull or not. Therefore analog 
line doesnt support any kind of authorisation (signalling) we can define success 
of call by 2 ways. The NLLW needs this info to not dial further numbers.   

First  way  (

no  confirmation

)  is  detection  that  call  was  succesfull  on  the 

base  control  ringing  tone  (CRT).  It  is  tone  which  we  are  hearing  in  handset 
when make call to other subscriber. Thed NLLW detects this tone And when is 
missing  for  certain  time  then  evaluate  the  call  was  succesfull  (Green  indicator 
light  up    and  yellow  light  down).  The  time  which  define  undetection  of  CRT  ( 
called part picks up) is adjustable because each type of PBX can be different. 
Usually  should  be  5  seconds  as  the  best.  At  this  call  authorisation  stays 
possibility  confirm  the  call  by  dial  confirmation  characters  (*xxxxxx,  where 

Содержание New Link Lift Watch 50

Страница 1: ...ALPHATECH TECHNOLOGIES s r o Jeremenkova 88 Praha 4 Czech Republic www alphatechtechnologies cz New Link Lift Watch Lift communicator User guide...

Страница 2: ...er PC via configuration software For connection the NLLW to PC you have to use special cabel After button pressing the NLLW enables to make phone call up 6 numbers max 16 digits in tone or pulse dial...

Страница 3: ...2 CALLING FROM LLW 19 2 2 1 Emergency call button activation 19 2 2 2 Calling from INPUT Failure call 19 2 2 3 Calling from INPUT Technical call 20 2 2 4 Service calling from timer 20 2 2 5 End of cal...

Страница 4: ...2 24V second mode is using only if you haven t power supply then you use power for current loop from telephone line CAUTION It is not galvanically isolated Third mode is external power for example but...

Страница 5: ...room call it is calling between lift cabin and machine room Incoming call it is calling coming from outside into NLLW unit The NLLW pick up you can programm parametres Dial it is kind of dial on telep...

Страница 6: ...uring TRH setting that incoming direction speaker and outgoing direction microphone are influence each other We recommend to dont set high volume in the begining of micro or speaker and via TRH set bo...

Страница 7: ...s possible choice from the current loop is powered Attention button is galvanic connect with source power of current loop and isolated from line by optocoupler In case powered current loop from teleph...

Страница 8: ...into loudspeaker Level from which volume with switch on direction from microphone doorphone setting trimmer TRH This setting interact level surrounding noise and setting gain of microphone MIC Progre...

Страница 9: ...voltage in Hang up status disconnect loop 20 60V during connection not depends on polarity when NLLW pick up active status on telephone line is cca 7 12V depends on line current which is in range 20...

Страница 10: ...e 10 1 3 5 Button and blocking connection BUTTON a BLOCK When telephone line is connected we need connect button only The button is connected to screw terminal mark BUTTON Look on picture 4 Picture 4...

Страница 11: ...ton is galvanic connect with source power of current loop and isolated from line by optocoupler In case powered current loop from telephone line is button galvanic connect with telephone line Picture...

Страница 12: ...puts for those indicators are isolated from other components and each from other as well The switchers are made until current 0 5A and voltage 50V On Picture 6 you can see examples of lamp indicator c...

Страница 13: ...of this voltage change before failure calling is activated INPUT is possible connecting up to 100m and is possible conecting moore butons switch on paralel or switch off buttons serial Control of type...

Страница 14: ...8 Connection of machine room communication 3WR When use in machine room modul PREPOJ you can see on picture 8 its connection From machine room to lift cabin must lead 3 wires Picture 8 Connection of m...

Страница 15: ...powering power 12 24V is possible and DC or AC voltage because telephone line has not enough power Screw 12V is isolated from other components and not depends on polarity Screw marks COM is share outp...

Страница 16: ...e 16 1 4 NLLW Installation The compact solution of NLLW enables easy installation into lift cabin panel Dimension and installation holes are descriped on picture 10 SPK MIC panel NLLW unit Picture 10...

Страница 17: ...three SPK MIC panels The lift cabin panel should be equiped by acoustic holes in microphone as same as speaker part It should be also provides by 4 screws M4 for fixing the SPK MIC panel The proper m...

Страница 18: ...lighting Command confirmation from phone 425 Dial DTMF Pulse Light off Call lighting x Notification of call ending 1275 lighting x Enter to programming mode from phone 850 Yellow lighting Programming...

Страница 19: ...ed It means when you programm numbers to all 6 position then progressivelly dial all 6 numbers When you erase number on position 3 then dial numbers on position 1 and 2 and returns back to position 1...

Страница 20: ...mber or all round of emergeny numbers then you have max 7 numbers The service calling is repeated in period 0 9 min programmable until succesfull call confirmation The repeated time between calls is p...

Страница 21: ...on box named PREPOJ and via connection of third wire telephone line has 2 wires And third is for NLLW controlling Wires connection is displayed on picture 8 page 15 The call is activated by picking up...

Страница 22: ...ametres The initial state for programming is signaled by programming tone and the guard will come back to this state always after time expiration 5 seconds even you started to program anything When pr...

Страница 23: ...line powering Procedure Connect the NLLW to the line Connect the NLLW with PC by KAB cable if PC serial port absent the USB COM reduction is to be used The NLLW will answer and LED light on the front...

Страница 24: ...Note Default 21 t nn Number nn in order p with confirmation t t call confirmation programm 0 1 only 0 confirmation OFF nn telephone number up 16 digits To programm other characters look on table Basi...

Страница 25: ...ers programmed in parameter 21 and 1 List of corresponding parametres 1 21 31 56 36 Parameter Value Note Default 33 i For failure calling are used also emergency numbers 0 i 0 emergency numbers are no...

Страница 26: ...position until empty or 6th position This is 1 sequence It might be repeated max 5 times List of corresponding parametres 1 Parameter Value Note Default 38 e Time of failure duration before failure c...

Страница 27: ...rameter Value Note Default 45 yyyyyy Confirmation character during dial in advance 66 yyyyyy confirmation character is numerals combination from 2 to 6 numerals List of corresponding parametres 1 21 2...

Страница 28: ...p always between rings It is 2 seconds after detection q th rings The number is adjustable from 1 to 9 List of corresponding parametres 44 Parameter Value Note Default 52 d Max call duration 2 d max t...

Страница 29: ...ks up the line and dialling the number range 1 5 sec This time is different for each PBX type but usually all PBXs works with time up 2 seconds List of corresponding parametres 8 85 Parameter Value No...

Страница 30: ...duration time ms range 1 0 it is 60 150ms m the time of space between tones is calculate insert number 5 x 10 space duration time ms range 1 0 it is 60 150ms f the time of Flash is calculate insert n...

Страница 31: ...ting for parametres 5x only 5 only Parameter 81 perform erasing of all numbers saved in memories of emergency service and failure call Parametres 83 85 perform selected default for parametres 3 5 only...

Страница 32: ...ng is switched off z 1 only tones pick up and hang up z 2 only other tones except pick up and hang up z 3 all tones they are switched on Parameter Value Note Default Ex 1 Ex 2 6 p polarity input buton...

Страница 33: ...cy call sequences 1 38 e The failure time duration before activation of failure calling 1 39 w Failure error call or Technical call 1 41 v Dial type v tone pulse 0 42 z Character to prolong a call 43...

Страница 34: ...rametres 5x only 5 only 9 E N D 5 Technical parametres 5 1 Elektrical parametres Parameter Value Conditions Min line current 18mA Line OFF HOOK Min line voltage 18V Line ON HOOK Line voltage when is N...

Страница 35: ...6 Emergency number position 3 Confirm 1 0 13 16 Emergency number position 4 Confirm 1 0 14 16 Emergency number position 5 Confirm 1 0 15 16 Emergency number position 6 Confirm 1 0 16 16 Service call n...

Страница 36: ...for relay switching from phone 48 2 Time of relay closing 49 2 Number of rings before picks up 51 1 Max call duration min 52 1 Time of button holding sec 53 1 Hanging up time when is redial sec 54 1 T...

Страница 37: ...Picture 11 Example of connection with LED blocking and failure is activated by voltage connection machine room communication...

Страница 38: ...TECHNOLOGIES s r o Jeremenkova 88 140 00 Praha 4 Czech Republic VAT CZ27577350 Company is registered in the Commercial Register administered by the Municipal Court in Prague Section C Record 116886 Ba...

Отзывы: