17
We reserve the right to modify technical specifications without prior notice.
UK830637/210804 – Translation of the operating manual © Alpha-InnoTec GmbH
for further information, see the sticker on the
electric heating element.
1 Sticker on electric heating element
After completion of all electrical installation work,
close the switch cabinet inside the unit.
close the front panel of the unit if no further
installation work inside the unit is to be performed
immediately.
1 Regulator connection, compressor
load, heating element load
2 Regulator board: connections
for sensors, pumps...
Terminal diagram, circuit diagram for respective
model
note.
the control element of the heat and
heat pump regulator can be connected
with a computer or network using an
network cable designed for such purposes,
therefore allowing the heating and heat
pump regulator to be controlled remotely.
If such a connection is desired, install
a screened network cable (category 6,
with rJ-45 plug) through the unit when
installing the connections and run it
through the front façade of the unit,
parallel to the already-present heating
and heat pump regulator control cable.
note.
electric heating element is connected to
6kW in the factory (except WZs 41H/sX
to 2kW). It can be re-connected to to 2,
4 or 6 kW at the contactor of the electric
heating element.