017-882-B0-001 Rev. E (06/2018)
2.0 Installation, Continued
2.2.7 Communications DOCSIS Status Monitoring
1.
Connect Battery Sense Wire Harness to the A/B, C/D connection points (14) on the transponder. The connection
(14) is not required for individual battery monitoring if the Smart AlphaGuard option is deployed. For XM3 units
with the Smart AlphaGuard option, connect the Battery Harness (5) to the AlphaGuard connection located on the
left side of the XM3 power supply, see Fig. 2-4.
2.
Connect Tamper Switch Wire Harness to the TPR Connector (18).
3.
Connect the RF drop (15) and make front panel connections as shown below for the DSM3 or IDH4. The DOCSIS
specification for downstream power level is +/-15 dBmV. However, for optimal performance, set the level as close to
0 dBmV as possible.
DOCSIS Status Monitor Front Panel Connections
Fig. 2-31, DOCSIS Status Monitor Front Panel Connections
ALM/
RDY
TPR
ENV
RST
A/B
C/D
GRN = OK
BLUE = WARN
RED = OUT
ETH
RF
LNK
OL
US
DS
COM
To Battery Sense Wire
Harnesses
Tamper Switch Connector
Required
Grounded Surge Protector
(Alpha p/n 162-028-10 or equivalent)
14
15
18
RF Cable to Headend
20
19
Tri-color RF
Power Level LEDs
Ethernet Connector
9