47
017-882-B0-001 Rev. E (06/2018)
2.0 Installation, Continued
Fig. 2-13, Battery Sense Wiring, 36V, 2 Battery Configuration
+
+
+
+
-
-
-
-
1
2
3
4
5
6
7
8
+
+
-
-
black
(–)
red
(+)
black
(–)
red
(+)
1
2
3
4
5
6
7
8
AlphaCell 18v4 Battery sense wiring as part of a retrofit installation.
B1
B2
A1
A2
A1
Vbatt 3B [D] 36V
Vbatt 3A
[C] 36V
Vbatt 2A
[C] 24V
Vbatt 1A
[C] 12V
Vbatt 2B [D] 24V
A/B (C/D) NEG
A2
Vbatt 1B [D] 12V
A/B NEG
Vbatt 2A
[C] 24V
Vbatt 1A
Vbatt 3A
[C] 36V
Fig. 2-14, Battery Sense Wiring, 36V, 4 Battery Configuration
The AlphaCell XTV 18V4 does not support
the Smart AlphaGuard (SAG) battery charge
management function. The SAG functionality
will be disabled in XM3 Power supplies
configured with Platform 14 firmware code.
To avoid possible alarms, the SAG should be
disconnected and the sense harness replaced
with a standard DSM harness connected to the
Battery A/B, C/D connector on the DM3X If the
SAG is still installed, selecting the 18V battery
will result in a SAG Compatibility alarm.
NOTICE
:
DM3X A/B, C/D
Connector
DM3X A/B, C/D
Connector
to
power
supply
to
power
supply
Each AlphaCell XTV 18V4 is shipped with a jumper
cable to be used in dual string configurations.
NOTICE
: