19
C048-781-30 R01, Rev. B (01/2020)
5.7
5.7 Review System Status via the Embedded Web Server
Review System Status via the Embedded Web Server
The optional embedded Ethernet module provides remote monitoring via IP-based Ethernet networks and a web browser.
To view the system status, you will need to connect the Ethernet port on the rear of your v30/30 distribution panel to your
network. By default, the Ethernet module is configured from the factory with a static IP address and network settings, as
defined below.
5.7.1
5.7.1 Default Static Network Settings
Default Static Network Settings
Use these default settings to set up a local network to communicate with the embedded web server:
y
IPV4 Address:
192.168.123.123
y
Subnet Mask:
255.255.255.0
y
Default Gateway:
192.168.123.1
y
Primary DNS:
192.168.123.1
y
Secondary DNS:
8.8.8.8
Once you establish a connection to the embedded Ethernet module,
use the following credentials to gain access to the protected data and
administrative pages:
y
Username:
root
y
Password:
password
5.7.2
5.7.2 Real-time Status
Real-time Status
Upon loading the v30/30 web server, the real-time status will be
displayed.
Site Information
User can configure these settings under Administration --> Site Settings.
y
Site name
y
Site location
Bus Detail
y
Voltage
y
Feeder fuse size
y
Load
y
Alarm threshold %
y
Load % based on feeder fuse size
Internal Temperature Sensor
y
Controller temperature sensor in Fahrenheit and Celsius
External Temperature Sensor
y
Up to (4) external temperature sensors in Fahrenheit and Celsius
Module Detail
y
SNMP channel mapping
y
Channel no.
y
Load per channel
y
Ampacity per channel
y
Breaker inventory status
y
Breaker status (ON/OFF)
Figure 30. Real-time Status
Figure 31. Temperature Sensors
Figure 32. Module Detail