Alpha CD24/32 - Fault Finding
10.5 FAULT FINDING SOLUTIONS F to K
YES
Check and correct:-
1. Ignition electrodes and leads
2. Electrode connections
3. Spark gap and position
4. Connections at ignition generator and PCB connector X7
F
Is spark generator (T2)
making a clicking noise
PCB, X7 connector is 200V ac
across terminals 22, 23 during ignition
Replace PCB
Replace ignition
generator
NO
NO
YES
YES
Check and correct:-
1. Check polarity of electrical supply
2. Flame sensing electrode and lead connections
3. Electrode position
4. Blockage of pressure tubes
G
Replace PCB
H
Replace pump
Allow to cool.
Continuity across
thermostat terminals
Replace overheat thermostat
NO
YES
Vent air, clear blockage
YES
Air in main heat exchanger,
blocked heat exchanger/pipework
or pump not circulating water
NO
YES
240V at internal clock
terminals 1 and 2
I
240V at PCB - X1 connector,
terminals 55 and N
240V at PCB - X1 connector,
terminals 34 and N
Wiring between clock
and PCB is correct
YES
YES
NO
YES
Continuity across
clock terminals 3 and 4
Internal clock calling
for heat
Wiring between clock
and PCB is correct
Replace clock
Check external controls
are calling for heat
YES
YES
NO
J
Replace primary pressure switch
Replace PCB
Continuity across primary
pressure switch terminals
36 V DC at PCB across
X9 connector terminal 45
and X8 connector terminal 46
YES
NO
NO
K
DHW flow valve
diaphragm damaged
Diverter valve
spindle assy. fault
Diverter valve
spindle operating
Replace diaphragm
Replace diverter valve
YES
YES
YES
Continuity across DHW
switch at inline connector
Replace PCB
Replace DHW switch
36 V DC between
PCB - X8 connector,
terminals 46, 47
YES
NO
NO
NO
NO