21
5.3
TEST FOR GAS SOUNDNESS AND PURGE THE SUPPLY
1.
With the boiler gas service cock closed (slot at right angles to valve). Pressure test the gas supply and inlet pipework
connection to the boiler gas service cock for soundness in accordance with BS 6891.
2.
Loosen the gas inlet pressure test point screw on the gas valve (see Fig. 24). Ensure the gas supply is on and open the
boiler service cock to purge in accordance with BS 6891.
3.
Retighten the test point screw and test for gas soundness. Close the boiler gas service cock.
5.4
INITIAL LIGHTING - Refer to Fig. 22 or 23
1.
Ensure that the gas and electrical supplies to the boiler are off and that the mains water inlet valve and the central heating
flow and return valves are open.
2.
Turn on the gas and electrical supplies to the boiler.
3.
Ensure all external controls are calling for heat.
CD24C and CD32C only - If the optional Clock is fitted, refer to the User's instructions, set the time and ensure the Clock
is in an 'on' mode.
4.
Set the hot water and central heating thermostats to maximum.
5.
CD24C and CD32C only - Set the selector switch to
(DHW only). Open a hot water tap, the main burner will light and
the boiler will provide hot water. Close the tap and the burner will go out.
6.
Set the selector switch to
(CH and DHW) or 'ON' on the CD24S boiler. The boiler will now run in the central heating
mode. The pump will start, the fan will start and the main gas valve solenoid will open allowing the main burner to light.
5.5
CHECK THE BURNER PRESSURES - Fig. 24
Turn the boiler off. Loosen the burner pressure test point screw on the gas valve and connect a pressure gauge. Allow the
boiler to run for 10 minutes and check the burner pressures.
Hot water mode - CD24C and CD32C only
1.
Set the selector switch to
(DHW only) and fully
open a hot water tap.
2.
The burner will light at the ignition rate and the
burner pressure will increase to maximum.
3.
Gradually close the hot tap and check that the burner
pressure decreases to its minimum. Fully open the
tap and check that the burner pressure increases.
Close the tap and check that the burner goes off.
Note: The burner pressure settings have been
factory set and do not require adjusting. If
incorrect, check that the inlet gas pressure is 20
mbar.
If the inlet gas pressure is not 20 mbar, either the
pipework is too small or the gas supply to the house is insufficient, in which case contact your gas supplier.
Central heating mode
1.
Set the selector switch to
(DHW and CH) or 'ON' on the CD24S boiler.
2.
The burner will light at the ignition rate and will increase to the factory pre-set maximum output after 1 minute.
3.
Turn off the boiler. Disconnect the pressure gauge and tighten the test point screw.
Test for gas soundness using suitable leak detection fluid.
Note: Refer to Technical Data, section 2.1 for burner pressure settings.
Alpha CD24/32 - Commissioning
Fig. 24
Burner pressure test point
Inlet gas pressure test point