25
Subject to change without notice | 83056700fUK – Translation of the original operating manual | ait-deutschland GmbH
Performance data: Heating output / COP
SWC 82(H)(K)3
SWC 102(H)(K)3
at B0/W35 operating point to EN14511
kW ı COP
7,70 ı 4,90
9,34 ı 5,05
at B0/W45 operating point to EN14511
kW ı COP
6,84 ı 3,61
8,84 ı 3,80
at B0/W55 operating point to EN14511
kW ı COP
6,49 ı 2,91
8,30 ı 2,82
at B7/W35 flows analogous to B0/W35
kW ı COP
9,20 ı 5,96
11,19 ı 6,30
Cooling capacity at max. flow rate (B15/W25), units with passive cooling: Identifier K
kW
7
8,6
Limits of use
Heating circuit return min. I Heating circuit flow max.
°C
20 I 60
20 I 60
Heat source return
min. I max.
°C
-5 – 25
-5 – 25
additional operating points
…
B0W65
B0W65
Sound
Sound pressure level at 1m distance from edge of unit
dB(A)
31
32
Sound power level to EN12102
dB(A)
43
44
Heat source
Flow rate: minimum I
nominal analogous to B0/W35
I maximum
l/h
1200 ı
1750
ı 2600
1500 ı
2200
ı 3300
Max. free heat pump pressure ∆p (with cooling ∆pK) ***) ı Flow rate
bar (bar) ı l/h
0,76 (0,70) ı 1750
0,93 (0,86) ı 2200
Approved anti-freeze
Monoethylene glycol I Propylene glycol I Methanol I Ethanol
• I • I • I •
• I • I • I •
Anti-freeze concentration: Minimum frost protection down to
°C
-13
-13
max. allowable operating pressure
bar
3
3
Heating circuit
Flow rate: minimum I
nominal analogous to B0/W35
I maximum
l/h
650 ı
1300
ı 1600
800 ı
1600
ı 2000
Max. free heat pump pressure ∆p (with cooling ∆pK) ı Volume flow
bar (bar) ı l/h
0,57 (0,54) ı 1300
0,52 (0,48) ı 1600
Pressure losses, heat pump ∆p ı Volume flow
bar ı l/h
— (—) ı —
— (—) ı —
max. allowable operating pressure
bar
3
3
General unit data
Total weight (with cooling)
kg (kg)
175 (183)
180 (188)
Box weight (with cooling) ı Tower weight (with cooling)
kg (kg) ı kg (kg)
110 (118) ı 65 (65)
115 (123) ı 65 (65)
Refrigerant type ı Refrigerant capacity
… ı kg
R410A ı 1,72
R410A ı 1,98
Domestic hot water tank
Net volume
l
—
—
Impressed current anode
integrated: • yes — no
—
—
Domestic hot water temperature, heating pump mode I Electric heating element
up to °C ı up to °C
— I —
— I —
Mixed water quantity according to ErP: 2009/125/EC (at 40°C, draw-off of 10 l/min)
l
—
—
Standing loss according to ErP: 2009/125/EC (at 65°C)
W
—
—
Maximum pressure
bar
—
—
Electrics
Voltage code ı all-pole heat pump fusing *)**)
… ı A
3~PE/400V/50Hz ı C10
3~PE/400V/50Hz ı C10
Voltage code ı Control voltage fusing **)
… ı A 1~N/PE/230V/50Hz ı B10
1~N/PE/230V/50Hz ı B10
Voltage code ı Electric heating element fusing **)
… ı A 3~N/PE/400V/50Hz ı B16
3~N/PE/400V/50Hz ı B16
Voltage code ı all-pole fusing for connection via a joint supply cable*)**)
… ı A
— ı —
— ı —
WP*): effect. Power input at B0/W35 to EN14511 I Current input I cosφ
kW ı A ı …
1,57 ı 3,02 ı 0,75
1,87 ı 3,73 ı 0,72
WP*): Max. machine current I Max. power input within the limits of use
A ı kW
6,01 ı 3,10
7,63 ı 4,00
Starting current: direct ı with soft starter
A ı A
30,0 ı —
— ı 22,0
Degree of protection
IP
20
20
Electric heating element output
kW
9 ı 6 ı 3
9 ı 6 ı 3
Circulation pump power consumption, heating circuit I heat source
min. — max.
W ı W
2 – 60 ı 3 – 140
2 – 60 ı 2 – 180
Other unit information
Safety valve, heating circuit I Heat source
included in scope of supply: • yes — no
— I —
— I —
Expansion valve, heating circuit I Heat source
included in scope of supply: • yes — no
— I —
— I —
Overflow valve I Changeover valve, heating -Domestic hot water
integrated: • yes — no
• I •
• I •
Vibration isolators, heating circuit I Heat source
integrated: • yes — no
• I •
• I •
*) Only compressor, **) Follow local regulations, ***) Figures for 25% mono-ethylene glycol
813467a
813468a
Heating capacity ı COP
SWC 82(H)(K)3 – SWC 102(H)(K)3
Technical data / Scope of supply