11
Subject to change without notice | 83054200iUK | ait-deutschland GmbH
16.3 Installation
CAUTION
In the air outlet area the air temperature is
approx. 5 K below the ambient temperature.
Under certain climatic conditions, an ice lay-
er can therefore form in the air outlet area.
Install the heat pump such that the air blow-
er does not discharge into footpath areas.
IMPORTANT
Do not tilt the unit more than a maximum
of 45° (in any direction).
NOTE
Always observe the installation plan for the
respective unit model. Note the size and min
-
imum clearances.
“Installation plans“, from page 29, for respec
-
tive unit model
Set up the unit so that the switch box side is accessi
-
ble at all times.
16.4 Attaching the air flow baffles
WARNING
Unit has rotating parts.
For safety reasons, mount the two air flow
baffles on the unit before continuing with
any other work.
1. If you have not already done so, remove lower
facing panels on the switch box and water con
-
nection side of the unit.
1.1. To do so, loosen the two quick-release screws on
the lower facing panels.
1.2. Pull each facing panel forward, detach from the
unit and set securely aside.
1 lower facing panels
2. Remove upper facing panels from unit.
2.1. To do so, loosen the two screws on the lower edg
-
es of the upper facing panels.
2.2. Pull each facing panel downward and forward, de
-
tach from top cover of unit and set securely aside.
1 top cover of unit
2 upper facing panels
3. The top cover of the unit was fastened by the up
-
per facing panels. After removal of the upper fac
-
ing panels, the top cover is loose. Remove top
cover and set securely aside.
Содержание LW 140A
Страница 1: ...UK 83054200iUK Air Water Heat Pumps Outdoor installation Operating Manual LW 140A LW 251A...
Страница 21: ...21 Subject to change without notice 83054200iUK ait deutschland GmbH...
Страница 32: ...32 Subject to change without notice 83054200iUK ait deutschland GmbH LW 140A LW 251A Row tank...
Страница 33: ...33 Subject to change without notice 83054200iUK ait deutschland GmbH Separate buffer tank LW 140A LW 251A...