TPM 083/12

3

II. GENERAL INFORMATION

1. Description

1.1.  

Fire dampers are shutters in piping systems of air-conditioning devices that prevent spreading 
the fire and combustion products from one fire segment to the other one by means of closing the 
air piping in the points of fire separating constructions.

1.4.  

The damper is sealed with a silicon packing against smoke penetration after closing the blade. At 
the same time, the damper blade is bed in a material which enlarges its capacity and air proofs 
the air duct.

1.3.  

Dampers  blade  automatically  closes  air  duct  using  an  actuating  mechanism  back  spring.  The 
back spring of the actuating mechanism is started when the thermoelectrical starting mechanism 
BAE 72B-S is activated, when a reset button on BAE 72B-S is pushed or when a power supply 
of the actuating mechanism is stopped.

1.5.  

Dampers have one inspection hole, since the shutting device and the inspection hole can be set 
into  the  most  advantageous  position  (with  respect  to  the  operation  and  manipulation  with  the 
control device).

1.6.  

Exact damper function is provided under the following conditions:

 

  

a) Maximum air circulation speed: 12 m.s

-1

 

  

Maximum pressure difference: 1200 Pa

 

  

b) Dampers could be displaced into position “CLOSED” only in case that ventilator, or Air 

  

  Handling  Unit  is  switched  off.  The  goal  is  the  securing  of  proper  closing  and  safe 

  

  function of Fire Damper in case of Fire.

 

  

 

  

c) The  air circulation in  the whole damper section  must be  secured as steady on  whole 

  

  surface.

1.7.  

Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3.

1.8.  

Dampers are suitable for systems without abrasive, chemical and adhesive particles.

1.9.  

Temperature in the place of installation is permitted to range from - 20°C to + 50°C.

1.11.  

In this document are used next signs and units.

1.10.  

If is not noticed other way, all dimensions and weight are in millimeters and kilograms.

Key :

w

[m.s

-1

]

air velocity

  p

[Pa]

pressure loss

L

w

[dB]

level of acoustic output

[ ]

pressure loss coefficient

[kg.m

-3

]

density

D, a

[mm]

dimension

[m

2

]

area

1.2.  

Basic dampers parameters

 

- fire damper tests provided according to EN 1366-2 and EN 15650.

 

- fire damper classified according to EN 13501-3 + A1 as

 

  

EI 60 (ve ho i    o) S

 

 - casing (external) leakage classified as class C according to EN 1751

 

- closed blade (internal) leakage classified as class 2 according to EN 1751

 

- fulfil all the prescribed requirements of EN 15650, art. 4.2.2. Protection against corrosion 

 

- dampers are classified as C10000 (cycling test) according to EN 15650

Содержание MANDIK FDMC

Страница 1: ...0 1 0 A L N O RS y s t e myWe n t y l a c j i S p z o o A l e j aK r a k o w s k a1 0 0 5 5 5 2Wo l aMr o k o w s k a t e l 2 27 3 7 4 0 0 0 f a x 2 27 3 7 4 0 0 4 w w w a l n o r c o m p l F I R E D...

Страница 2: ...tement of installations 9 III TECHNICAL DATA 10 6 Pressure loss 10 7 Coefficient of local pressure loss 11 8 Noise data 11 9 Electrical Components Connection Diagrams 13 IV ORDERING INFORMATION 16 10...

Страница 3: ...mum pressure difference 1200 Pa b Dampers could be displaced into position CLOSED only in case that ventilator or Air Handling Unit is switched off The goal is the securing of proper closing and safe...

Страница 4: ...whole system Nonpotential auxiliary contacts enable connection to the master control system signalisation of the damper position failure reports release of the ventilators etc While a flashing green...

Страница 5: ...LURE If the fire dampers do not reach the given position in time tolerable for displacing the appropriate light diode FAILURE starts to flash and K1 contact is opened current failure In case that the...

Страница 6: ...3 12 6 Fig 1 Fig 2 Fire damper FDMC 3 Dimestions weights 3 1 Dimensions Position 1 Damper body 4 BAE 72B S thermoelectrical starting mechanism 2 Damper blade 5 Inspection hole covering 3 Actuating mec...

Страница 7: ...ampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire separating constructions Damper assembly procedures must be done so as all load transfer from the...

Страница 8: ...ng or closing 4 6 Installation opening dimensions 4 2 To provide needed access space to the control device all other objects must be situated at least 350 mm from the control parts of the damper Inspe...

Страница 9: ...een damper and wall is filled by mortar gypsum EIS 60 8 Damper installed in a ceiling wall construction min thickness 150 mm Space between damper and wall is filled by mortar gypsum EIS 60 9 Position...

Страница 10: ...6 2 1 Pressure losses for air density 1 2 kg m 3 6 Pressure loss 6 1 Pressure loss calculation III TECHNICAL DATA 6 2 Determination of pressure loss by using diagram 6 2 1 1 2 kg m 3 p w2 2 p Pa pres...

Страница 11: ...53 3 55 1 56 5 57 7 6 34 8 40 2 43 3 45 6 48 7 51 0 52 7 55 8 58 1 59 8 61 2 62 4 7 38 8 44 2 47 3 49 6 52 7 55 0 56 7 59 9 62 1 63 8 65 2 66 4 8 42 3 47 7 50 8 53 1 56 2 58 4 60 2 63 3 65 6 67 3 68 7...

Страница 12: ...b 8 3 2 Correction to the weight filter A w m s 1 2 3 4 5 6 7 8 9 10 11 12 KA dB 15 0 11 8 9 8 8 4 7 3 6 4 5 7 5 0 4 5 4 0 3 6 Tab 8 3 3 Relative level expressing the shape of the spectrum Lrel f Hz w...

Страница 13: ...s Protection Class III II Degree of protection IP 54 Running time motor spring return 40 75 s 20 s Ambient Temperature normal duty safety duty non operating temperature 30 C 50 C The safe position wil...

Страница 14: ...lug of 26 type 6 pole plug 3 pole plug screw terminals for conductor 2x1 5 mm2 9 2 Communication and Supply Device Fig 15 Communication and Supply Device BKN 230 24 9 3 Communication and Control Devic...

Страница 15: ...l Device BKS 24 9A Communication and Control Device BKS 24 9A Nominal voltage AC 24 V 50 60Hz Power consumption 3 5 W operating position Dimensioning 5 5 VA Protection Class III safe small voltage Deg...

Страница 16: ...Device BKS 24 9A technical specifications design acc dle Tab 2 3 1 size type FDMC 180 TPM 083 12 40 V DATA OF THE PRODUCT 11 Data label 11 1 Data label is placed on the body of fire damper Fig 18 Data...

Страница 17: ...ulated During transportation the damper blade must be in the CLOSED position VIII TRANSPORTATION AND STORAGE 14 2 Dampers are stored indoor in environment without any aggressive vapours gases or dust...

Страница 18: ...off the actuating mechanism supply e g by pressing the RESET button at the thermoelectrical starting mechanism BAE 72B S or cutting off the supply from ELECTRICAL FIRE SIGNALISATION Check of blade di...

Страница 19: ...TPM 083 12 19...

Страница 20: ...z o o A l e j a K r a k o w s k a 1 0 0 5 5 5 2Wo l a M r o k o w s k a P o l s k a T e l 4 82 2 7 3 7 4 0 0 0 F a x 4 82 27 3 7 4 0 0 4 E M a i l a l n o r a l n o E M a i l a l n o r a l n o r c o m...

Отзывы: