TPM 083/12
9
Tab. 5.1.1. Statement of installations
Size
FDMC installation
Classifi-
cation
Figure
100-400
Damper installed in a solid wall construction min. thickness 100 mm.
Space between damper and wall is filled by mortar, gypsum.
EIS 60
7
Damper installed in a gypsum wall construction - fire classification EI 90.
Space between damper and wall is filled by mortar, gypsum.
EIS 60
8
Damper installed in a ceiling wall construction min. thickness 150 mm.
Space between damper and wall is filled by mortar, gypsum.
EIS 60
9
Position:
1
Fire damper FDMC
2
Mortar or gypsum with min. density 800 kg/m
3
Fig. 7
Damper installed on a solid wall construction
2
1
2
1
Position:
1
Fire damper FDMC
2
Mortar or gypsum with min. density 800 kg/m
3
Fig. 8
Damper installed on a gypsum wall construction
5. Statement of installations
5.1.
Statement of installations
2
1
2
1