Allora Positive Contact PCS-250 Скачать руководство пользователя страница 6

OK LED (

See Relay Control Switches Below)

The OK LED will illuminate at power on. When a start signal 
is initiated the LED will momentarily turn off. If a good 
condition has been detected the LED will again illuminate.

FAULT LED (

See Relay Control Switches Below)

When a fault or broken tool condition is detected the FAULT 
LED will illuminate momentarily or until the unit is reset if the 
relay is set to Latch.

TEACH LED and Push Button

After the sensor has been installed you must teach the 
system the location of the tool or object to be monitored. 
Push the teach button one time, and the teach LED will 
illuminate. Push the teach button again and the sensor will 
begin its learn cycle. A start signal can also be applied to 
begin the learning cycle. The system stores the information 
in memory and does not require another learning cycle 
when power has been removed.

Sensor Control Unit Switches

Relay  Control Switches

These switches are used to set condition and the operation of the controls internal relays

These feature has been added for increased interface flexibility 

FAULT Relay Contact Configuration
NO= Normally open
NC= Normally closed

OK Relay Contact Configuration
NO= Normally open
NC= Normally closed

FAULT Relay Operation
M= Momentary
L= Latch

OK Relay Operation
M= Momentary
L= Latch

Time Switches

These switches control the amount of time the sensor rotates during the scanning sequence. Since it takes a 
greater amount of time to swing the sensing needle 180º than 90º a greater amount of time needs to be set. If 
the sensor will not reach its end or fault position with the tool removed simply set  more time. NOTE:  If a TIME 
selection has not been made the Control Unit operates at a default LO-LO setting used for very small micro-
drill applications only.  (See LO/HI Switch settings below with regards to V-seal in Swing Arm Assembly).

NT / ET Switch

Selects the tolerance width relative to the taught value. NT = Normal Tolerance  ( factory preset ) 
ET = Extended Tolerance. This feature is used when monitoring multiple tools of different diameter, 
primarily on CNC machining centers.

CW / CCW Switch

This switch selects the desired swing rotation of the sensor. 

LO / HI Switch

Selects the rate at which the sensor swings. “LO” rate is a slower swing rate generally used for micro 
tool detection. NOTE: The V-seal in the swing arm assembly provides additional protection against 
contaminants and should not be removed in most applications.  The V-seal may however restrict the 
sensors motion when the swing rate is set on “LO”. If your application does not allow “HI” rate 
operation, you may remove the V-seal from the swing arm assembly to determine if this solves the 
problem.

OK

FAULT

TEACH

CW

LO

NT

TIME

CCW

1

2

3

HI

ET

NC

NC

L

L

NO

NO

M

M

Page 5

Please Note:  Unless otherwise specified when ordered, the TCU-250 Control Unit 

has been preset with a CW direction, #2 Time Setting and a HI Rate.

Содержание Positive Contact PCS-250

Страница 1: ...0 OK FAULT TEACH POWER 24VDC CW LO NT TIME FAULT OUTPUT OK OUTPUT COM 0 BLUE BLACK BROWN WHITE GRAY 1 2 3 4 6 5 4 3 2 1 CCW 1 2 3 HI NO NO NC NC M M L L TEACH RESET START 115V 24V ET USA Made in the P...

Страница 2: ...raight connector available upon request PCS 250 SENSOR 40MM 1 57 10MM 0 393 140MM 5 50 120MM 4 72 28MM 1 102 37 5MM 1 475 27MM 1 062 5 0M 16 0 TCU 250 OK FAULT POWER 24VDC CW LO NL TIME FAULT OUTPUT O...

Страница 3: ...ace available in the tooling area will determine the easiest mounting method and location With all machine power off hand hold the sensor in the tooling area to imagine its best placement Remember the...

Страница 4: ...to be repositioned while attached to the sensor rotate the entire sensor to avoid damage to the connector Make sure that the dip switch on the control unit is set to correspond to the CW or CCW direc...

Страница 5: ...application T 16 is the common for either a 115VAC start signal T 14 or a 24VDC start signal T 15 The TCU recognizes a change of state in the circuit to activate the checking sequence A minimum durat...

Страница 6: ...ount of time the sensor rotates during the scanning sequence Since it takes a greater amount of time to swing the sensing needle 180 than 90 a greater amount of time needs to be set If the sensor will...

Страница 7: ...d 115VAC machine control voltages For any questions or installation assistance contact 1 855 866 5911 TCU 250 OK FAULT TEACH POWER 24VDC CW LO NL TIME FAULT OUTPUT OK OUTPUT COM 0 BLUE BLACK BROWN WHI...

Страница 8: ...gnal Terminals 14 16 are for a 115VAC start signal Is the correct start signal being applied The signal can be AC or DC voltage Polarity does not matter The TCU 250 can be started with a low high low...

Страница 9: ...l The TCU 250 will run through one cycle the yellow light will turn off and the green light will illuminate The TCU 250 is now taught that tool s current position Is the tool within the PCS 250 s swin...

Страница 10: ...d mounting bracket for the Filter Regulator Gage is included with AP 1000 Kit Connect the provided NPT fitting into the filter regulator gage in the normal fashion Cut the tube to the required length...

Страница 11: ...ingle AP Sensors are supplied with an air tube and a NPT fitting for connection to the filter regulator Some machines may utilize more than one sensor One Allora AP 1000 Kit or customer supplied equiv...

Страница 12: ...ompliant materials They are free of Bromide Halogens PBB PBDE Mercury Cadmium and Chrome 6 All Positive Contact products are Lead Free All Positive Contact products comply with current EU environmenta...

Отзывы: