MAXI LITE II 

SERIAL NUMBER 10-000001 & 11-000001 

Testing Engine Speed at the GFCI Receptacle. 
 

WARNING: Dangerous voltage and/or current may be present when a 

voltage test is being conducted. To reduce risk of serious injury or death from electrical 
shock, if you are not trained to safely work with high voltage, do not attempt any of these 
procedures. You must seek assistance from qualified personnel. 
 

The speed of the engine may be tested by using a multimeter with the scale set to read 
hertz. 

NOTE: Not all multimeters have Hertz scale. 

 

Set your multimeter to the Hertz ( H

z

 ) scale. While the engine is running and the light 

breakers turned off, insert your meter probes into the GFCI receptacle as shown in 

figure N.1

( Pg. 14). The meter should read 62.0 Hertz with no load on the engine. A 

reading of less than 62.0 Hertz indicates that the engine is not running with enough 
speed to create the necessary power to operate all of the lamps consistently. 
 
Slow engine speed may be caused by a number of factors: 

A. Incorrectly adjusted engine governor. Adjust governor as shown on the following 

page ( Figure D.1/Pg 15 ) until a reading of 62.0 H

is indicated on the multimeter 

display. 

B. Clogged or dirty air and or/fuel filters. Replace filters if there are any questions as 

to their condition. 

C. Dirty fuel. Drain fuel tank and fuel system and replace with known clean fuel. 

Replace fuel filter before re-starting the engine. 

D. Worn or damaged engine. If the above steps fail to correct the engine speed this 

may indicate a faulty engine. Contact your local servicing dealer for the make 
and model diesel engine in your light tower. Repair, build or replace as 
necessary. 

 

Note: Many Allmand light towers designed for use outside of North America operate at 
230 Volt + 10%s/ 50Hz. Engines on these models must be set for 52.0 Hz at no load per 
the above instructions. If you are unsure which voltage your light tower is designed to 
produce, contact a qualified electrician for assistance. 
 
 

 

Содержание 10-000001

Страница 1: ...2 Hot Cool Sensor Kubota DeepSea 1 wire 101069 Oil Sensor Kubota 905 1005 1105 340301 Oil Sensor Kubota Deep Sea 1 wire 101070 Fuel Shut Off Solenoid 920751 Electric Fuel Pump 103331 Radiator Kit JB 1...

Страница 2: ...tion that the voltage regulator will have to be replaced If the problem persists then proceed to testing or replacing the alternator ML II CSA CANADA SPEC LSC 2 1 Powers off LSC screen when starting u...

Страница 3: ...g from the generator to the main breaker look for a small 16 gauge black wire connected to the back side of the main breaker Black wire gets 120 from the main breaker to the orange wire and into the r...

Страница 4: ...er is tested good at both light and switches ensuring ballast is receiving sufficient voltage in 120 240 Power out of ballast to the capacitor and light circuit should measure 360 440 volts 10 is with...

Страница 5: ...fer to page 2 For further troubleshooting procedures A reading less than 120 volts 10 indicates that the generator may be malfunctioning or there can be an issue with the main circuit breaker pop out...

Страница 6: ...e the four screws holding the control panel faceplate in place and carefully pull the faceplate away from the control box Allow the faceplate to hang from the attached wiring Caution Do not allow any...

Страница 7: ...MAXI LITE II SERIAL NUMBER 10 000001 11 000001 Figure L 1...

Страница 8: ...MAXI LITE II SERIAL NUMBER 10 000001 11 000001 Figure L 2...

Страница 9: ...t seek assistance from qualified personnel If the previous procedure indicates proper voltage at the top Input main breaker terminals see figure M 1 and A 1 on the next page The meter reading should i...

Страница 10: ...MAXI LITE II SERIAL NUMBER 10 000001 11 000001 Continued from Pg 11 Figure A 1...

Страница 11: ...te the necessary power to operate all of the lamps consistently Slow engine speed may be caused by a number of factors A Incorrectly adjusted engine governor Adjust governor as shown on the following...

Страница 12: ...ge WARNING Dangerous voltage and or current may be present when a voltage test is being conducted To reduce risk of serious injury or death from electrical shock if you are not trained to safely work...

Страница 13: ...make and model diesel engine in your light tower for specific governor adjustment Figure D 1 CAT 1 1 Governor Throttle Kubota 905 1005 1105 Governor Throttle Note If the throttle or Governor is adjus...

Страница 14: ...strument with an insulated handle short the capacitor between the terminals to discharge any stored power Figure B 1 The capacitor may be freely handled after it has been discharged Select Ohms on you...

Страница 15: ...MAXI LITE II SERIAL NUMBER 10 000001 11 000001 Figure R 1 Working Capacitor tested 25 0 Figure B 1 Discharging Capacitor...

Страница 16: ...F 11 8KW AIR 650290 OIL 113867 FUEL 113874 FILTER KIT ALL FUEL CAT C1 1 8KW C1 5 NA NON TURBO 13KW AIR 102580 OIL 650304 FUEL 103155 FILTER KIT ALL THREE 108961 CAT 1 5 T 15KW CAT 2 2 20KW AIR PRIMARY...

Страница 17: ...heck engine operators manual for specific recommended lubricants Additional warranty information claim forms can be obtained on Allmand com Please contact Allmand Tech line for additional help and tro...

Отзывы: