Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and
may block the terminations.
IMPORTANT
NOTE:
All horizontal runs of exhaust pipe must slope back toward unit.
A minimum of 1/4” (6 mm) drop for each 12” (305 mm) of horizontal
run is mandatory for drainage.
NOTE:
Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE
:
Exhaust piping should be checked carefully to make sure
there are no sages or low spots.
EXHAUST PIPE
Horizontal Application
Figure 22
Use the following steps to correctly size vent pipe diameter.
Table 4
MINIMUM VENT PIPE LENGTHS
A96DF2V
MIN. VENT LENGTH*
045, 070, 090, 110
15 ft. or
5 ft plus 2 elbows
or 10 ft plus 1 elbow
* Any approved termination may be added to the minimum lengh listed.