508151-01
Issue 2104
Page 16 of 72
Ramping Option A (Factory Selection)
•
Motor runs at 50% for 30 seconds.
•
Motor then runs at 82% for approximately 7-1/2
minutes.
•
If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
•
Once demand is met, motor runs at 50% for 30
seconds then ramps down to stop.
OFF
OFF
1/2 MIN
50% CFM
COMPRESSOR DEMAND
7 1/2 MIN
82% CFM
100%
CFM
1/2 MIN
50% CFM
Ramping Option B
•
Motor runs at 82% for approximately 7-1/2 minutes.
If demand has not been satisfied after 7-1/2 minutes,
motor runs at 100% until demand is satisfied.
•
Once demand is met, motor ramps down to stop.
OFF
OFF
82%CFM
100% CFM
COMPRESSOR DEMAND
7 1/2 MIN
Ramping Option C
•
Motor runs at 100% until demand is satisfied.
•
Once demand is met, motor runs at 100% for 45
seconds then ramps down to stop.
OFF
OFF
100% CFM
100% CFM
45 SEC.
COMPRESSOR
DEMAND
Ramping Option D
•
Motor runs at 100% until demand is satisfied.
•
Once demand is met, motor ramps down to stop.
OFF
OFF
100% CFM
COMPRESSOR
DEMAND
Switches 11, 12 and 13 -- Heating Mode Blower Speed
--
The switches are factory set to the OFF position which
provides factory default heat speed. Refer to Table 10 for
switches 11, 12 and 13 that provided the corresponding
increases or decrease to both high and low heat demand.
Heat Speed
Switch 11 Switch 12 Switch 13
+24%
On
On
On
+18%
On
On
Off
+12%
On
Off
On
+6%
On
Off
Off
Factory Default
Off
Off
Off
-6%
Off
Off
On
-12%
Off
On
Off
-18%
Off
On
On
Table 10. Heating Mode Blower Speeds