508151-01
Issue 2104
Page 36 of 72
Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 - 4500 ft
Number of
90° Elbows
Used
1-1/2" Pipe
2" Pipe
2-1/2" Pipe
3" Pipe
Model
Model
Model
Model
45
70
90
110
45
70
90
110
45
70
90
110
45
70
90
110
1
15
10
n/a
n/a
56
41
24
n/a
85
85
63
28
103
102
83
83
2
10
n/a
51
36
19
80
80
58
23
98
97
78
78
3
n/a
46
31
14
75
75
53
18
93
92
73
73
4
41
26
9
70
70
48
13
88
87
68
68
5
36
21
4
65
65
43
8
83
82
63
63
6
31
16
n/a
60
60
38
3
78
77
58
58
7
26
11
55
55
33
n/a
73
72
53
53
8
21
6
50
50
28
68
67
48
48
9
16
1
45
45
23
63
62
43
43
10
11
n/a
40
40
18
58
57
38
38
NOTE:
Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
Table 19C.