507769-04
Page 40 of 53
Issue 1927
Table 15.
Burner Orifice Conversion Kits at Varying Altitudes
96G1DFE
Capacity
0 - 7,500 ft
(0 - 2,286 m)
7,501 - 10,000 ft
(2,286 - 3048m)
Natural to LP/
Propane
LP/Propane to
Natural
High Altitude
Natural Burner
Orifice Kit
High Altitude LP/
Propane Burner
Orifice Kit
All
11K50†
73W80*
51W01
11K45†
* Conversion requires installation of a gas valve regulator spring, which is provided with the gas
conversion kit.
† LP kits include low line pressure switch.
96G1 Pressure Switch Requirements at Varying Altitudes
96G1DFE
Capacity
0 - 4500 ft
(0 - 1,373m)
4501 - 7500 ft
(1371 - 2286m)
7501 - 10000 ft
(2286 - 3048m)
045
No Change
No Change
11J09
070
No Change
17V95
11U67
090
No Change
11U70
10U93
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure
switch from 0-4500 feet (0-1370 m).