Error Code: E3/F5
Description:
Fan Speed is Operating Outside of the Normal Range.
General Note:
When the indoor fan speed is to low (300 RPM) during normal operations, the unit will stop and the LED
will display the failure( E3). When the outdoor fan speed registers below 200 RPM or over 1500 RPM for an
extended period of time, the unit will stop and the LED will display the failure (F5).
YES
NO
YES
YES
Power off, then restart the unit aer 2 minutes.
Does a problem remain?
NO
Shut off the power supply, rotate
the fan by hand.
Check the wiring of fan motor.
Measure the voltage for
the fan motor from the PCB.
Is it within normal parameters?
NO
Replace the indoor/outdoor
PCB
YES
Replace the fan motor
Does it turn easily?
Find the cause of the problem and resolve it
Is it improperly wired?
Ensure proper connecons