Outdoor Unit
24 (610)
Air Outlet
Air Inlet
24
(610)
12
(305)
79
(2007)
1
12
(305)
1
Minimum rear clearance can be 6 inches (152 mm) when mounted
on brackets and with no obstructions on the other three sides.
Figure 1.
Outdoor Unit Clearances - Inches (mm)
Multiple Outdoor Units
Height of
Wall (C)
Unit
Height (A)
118 (2997)
(Minimum
)
Unit to
Wall (B
)
24 (610)
(Minimum)
60 (1500)
(Minimum
)
10 (254
)
(Minimum
)
10 (254
)
(Minimum
)
AIR
FLOW
AIR
FLOW
CLEARANCE NOTES FOR MULTIPLE UNITS:
If the height of the wall (C) is less than or equal to the height of the smallest unit (A), the distance from the unit to the wall (B) must be a minimum of 10 inches (254 mm).
If 1/2 the height of the unit (A) is less than the height of the wall (C), the distance from the unit to the wall (B) must be a minimum of 12 inches (305 mm).
If the height of the wall (C) is greater than the height of the unit (A), the distance from the unit to the wall (B) must be a minimum of 20 inches (508 mm).
Figure 2.
Multiple Outdoor Unit Clearances - Inches (mm)