![Allied 4DHV Mini-Split Series Скачать руководство пользователя страница 23](http://html.mh-extra.com/html/allied/4dhv-mini-split-series/4dhv-mini-split-series_service-manual_2901684023.webp)
508067-01
Issue 2016
Page 23 of 75
Systems and Terminal
Designations
System
Capacity
System Voltage
Number of
Conductors
Wire Type
Wire Gauge /
MCA
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
09K
115VAC
4
Stranded and
unshielded
16AWG / 16A
Outdoor to Main Power
L, N and GND
09K
115VAC
3
14AWG / 15A
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
12K
115VAC
4
16AWG / 15A
Outdoor to Main Power
L, N and GND
12K
115VAC
3
14AWG / 15A
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
09K
208/230VAC
4
16AWG / 10A
Outdoor to Main Power
L, N and GND
09K
208/230VAC
3
16AWG / 9A
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
12K
208/230VAC
4
16AWG / 11A
Outdoor to Main Power
L1, L2 and GND
12K
208/230VAC
3
16AWG / 9A
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
18K
208/230VAC
4
16AWG / 15A
Outdoor to Main Power
L1, L2 and GND
18K
208/230VAC
3
16AWG / 18A
Indoor to Outdoor Wiring
(Communication/Power)
1, 2, 3 and GND
24K
208/230VAC
4
16AWG / 20A
Outdoor to Main Power
L1, L2 and GND
24K
208/230VAC
3
14AWG / 18A
Indoor to Outdoor Wiring
(Power only) - L1, L2 and GND
36K
208/230VAC
3
16AWG
Indoor to Outdoor Wiring
(Communication only)
S1, S2 and GND
36K
208/230VAC
3
Stranded and
shielded
24AWG
Outdoor to Main Power
L1, L2 and GND
36K
208/230VAC
3
Stranded and
unshielded
10AWG / 30A
MCA = Minimum Circuit Amps
Table 5. Single Zone Installation Wiring Requirements
Isolate the power supply before accessing unit electrical terminals.
Install unit so that unit disconnect is accessible.
Follow all local and national codes, as well as this installation instruction, during installation. Do NOT overload electrical
circuit, as this may lead to failure and possible fire.
Use specified wiring and cable to make electrical connections. Clamp cables securely and make sure that connections
are tight to avoid strain on wiring. Insecure wiring connections may result in equipment failure and risk of fire. Wiring must
be installed so that all cover plates can be securely closed.
WARNING