Allied 2HP13 Скачать руководство пользователя страница 5

506162-02

Issue  0847

      Page  5  of   14

2.

The valves should be k ept in the "front seated"
(closed) position.  This will allow evacuation of the
refrigeration lines and the indoor coil, without
disturbing the factory charge in the outdoor unit.

3.

Follow the vacuum  pum p m anufacturer's
instructions.  Allow the pum p to operate until the
system  has been evacuated down to 300 m icrons.
Allow the pum p to continue running for an additional
15 m inutes.  Turn OFF the pum p and leave the
connections secured to the two (2) service valves.
After 5 m inutes, if the system  fails to hold 500
m icrons or less, check all connections for tight fit and
repeat the evacuation procedure.

4.

Isolate the vacuum  pum p from  the system  by closing
the shutoff valves on the gauge-set.  Disconnect the
vacuum  pum p.

Opening Service Valves

After evacuation of the connecting lines, rem ove the

service valve cap and fully insert the hex wrench into the
stem .  A back-up wrench is required on the valve body to
open the valve stem .  Back-out counterclockwise until the
valve stem  just touches the coined edge.

W rench sizes:

3/8 service valve:  3/16" Hex wrench
3/4 service valve:  5/16" Hex wrench
7/8 service valve:  5/16" Hex wrench

Replace service valve cap and torque to 8-11 ft-lb on 3/8"

valves; 12-15 ft-lb on 3/4" valves; 15-20 ft-lb on 7/8" valves.
Use backup wrench on valve body when torqueing valve
cap.

Install Electrical Accessories

Refer to the instructions packaged with the accessories.

Electrical Connections

Be sure to check all local codes to determ ine that the unit

is installed accordance with local requirem ents.  Consult
the National Electric Code for wire size requirem ents.  Use
60

/

 C wire or higher.  Always provide ground connections

to the outdoor unit.  Power supply m ust agree with rating
on unit nam eplate.

Provide line voltage power supply to unit from  a properly

sized disconnect switch.  Route power and ground wires
from  disconnect switch to unit.  Line voltage connections
are m ade at the line side of the contactor in the control box
of the outdoor unit.  Follow the appropriate wiring diagram
attached to inside of the access panel.

Proper circuit protection recom m endations are  indicated

on Unit Rating Plate. Tim e delay fuses are required to
prevent blowing due to starting current (the current in rush
when equipm ent starts is referred to as the Locked Rotor
Am ps or (LRA).  A fuse of this kind properly sized will give
m axim um  equipm ent protection.

Use copper wire only between disconnect switch and

unit.

Rem ove access panel to gain access to unit wiring.

Extend wires from  disconnect through power wiring hole
provided and into unit control box.  Flexible conduit is
required for the swing out control box feature.

Connect ground wire to ground connection in control box

for safety.  Connect power wiring to contactor.

High voltage power connections to 3-phase m odels is

m ade to "Pig Tail" leads with field supplied splice
connectors.

Control W iring

The control voltage is 24 Vac. NEC Class I insulated 18

AW G is required for control wiring.  For lengths longer than
150 feet, contact your local distributor for technical service.

Ensure the room  therm ostat is properly installed per

instructions shipped with room  therm ostat.  Generally the
therm ostat should not be exposed to sunlight, drafts or
vibration and should not be m ounted on exterior walls.

Low voltage control wire connections should be m ade to

the screw connection term inal board m ounted on the
defrost control as shown.  All low voltage control wiring
m ust be separated from  incom ing power leads.

. . . .

ELECTRICAL SHOCK HAZARD!

Turn OFF electric power before connecting unit,
performing any maintenance or removing
panels or doors.  More than one disconnect
may be required to turn off all power.

FAILURE TO DO SO COULD RESULT IN BODILY
INJURY OR DEATH.

T he unit cabinet m ust have an uninterrupted or
unbroken ground to m inim ize personal injury if an
electrical fault should occur.  The ground m ay consist
of electrical wire or m etal conduit when installed in
accordance with existing electrical codes.  Failure to
follow this warning can result in an electric shock,
fire, or death.

Содержание 2HP13

Страница 1: ...l Code Part 1 CSA C22 1 2HP13 14 4HP13 SPLIT SYSTEM HEAT PUMP INSTALLATION START UP INSTRUCTIONS HOMEOWNERS INFORMATION MANUAL TABLE OF CONTENTS These units are designed for use in residential and light commercial type buildings Heat Pumps may only be installed with indoor combinations listed in the Air Conditioning and Refrigeration Institute ARI Directory of Certified Products Inspect the unit f...

Страница 2: ...nnected to factory approved indoor unit outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field supplied tubing For proper unit operation check refrigerant charge using charging information located on control box cover IMPORTANT Maximum liquid line size is 3 8 in O D for all residential applications including long lines Outdo...

Страница 3: ...rant line lengths DO NOT LOCATE THE UNIT On brick concrete blocks or unstable surfaces Near clothes dryer exhaust vents Near sleeping area or near windows Under eaves where water snow or ice can fall directly on the unit with clearance less than 2 ft from a second unit with clearance less than 4 ft on top of unit Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 F and t...

Страница 4: ...th water using a wet rag Leave rag on fitting body and re wet with water to help cool area Leak Check Refrigeration lines and indoor coil must be checked for leaks after brazing and before evacuation The recommended procedure is to apply a trace amount of vapor refrigerant approximately two ounces or 3 psig into the line set and indoor coil then pressurize with 150 psig of dry nitrogen Use a refri...

Страница 5: ... at the line side of the contactor in the control box of the outdoor unit Follow the appropriate wiring diagram attached to inside of the access panel Proper circuit protection recommendations are indicated on Unit Rating Plate Time delay fuses are required to prevent blowing due to starting current the current in rush when equipment starts is referred to as the Locked Rotor Amps or LRA A fuse of ...

Страница 6: ...or line sets shorter than 15 feet in length remove charge For line sets longer than 15 feet add charge Oil charge is sufficient for all line lengths Before final adjustment is made to the refrigerant charge it is imperative that proper indoor airflow be established Airflow will be higher across a dry coil versus a wet coil Blower charts are calculated with a dry or wet coil basis Recommended airfl...

Страница 7: ...ously Filter Drier The outdoor unit is equipped with a bi flow filter drier If replacement is necessary order new dryer according to the service parts manual Emergency Heat Function Room Thermostat An emergency heat function is designed into some room thermostats This feature is applicable when isolation of outdoor unit is required or when auxiliary electric heat is staged by outdoor thermostats W...

Страница 8: ... seconds going in and out of the defrost mode when the compressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The timed off delay is 5 minutes long The delay help to protect the compressor from short cycling in case the power to the unit is interrupted or a pressure switch opens The delay is bypassed by placing the timer select jum...

Страница 9: ...506162 02 Issue 0847 Page 9 of 14 H P SINGLE PHASE WIRING DIAGRAM ...

Страница 10: ...506162 02 Issue 0847 Page 10 of 14 H P 3 PHASE WIRING DIAGRAM ...

Страница 11: ... manufacturers The information below is typical for most thermostats Ask your dealer for specific information regarding the model of thermostat installed Temperature Setting Levers Most heat pump thermostats have 2 temperature selector levers one for heating and one for cooling Set the levers or dials to the desired temperature set points for both heating and cooling Avoid frequent temperature adj...

Страница 12: ...s dryers and fall off from trees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and could cause damage to the condenser Periodically debris should be brushed from the condenser coils Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Damaged or bent fins may affect unit operation Painted Surface...

Страница 13: ...lete model and serial number b proof of required periodic maintenance installation date and location c an accurate description of the problem W ARRANTY LIMITATIONS 1 This warranty is void if the covered equipment is removed from the original installation site 2 This warranty does not cover damage or defect resulting from a flood wind fire lightning mold or installation and operation in a corrosive...

Страница 14: ...506162 02 Issue 0847 Page 14 of 14 NOTES ...

Отзывы: