506892-01
Page 33 of 64
Issue 1251
Integrated Control DIP Switch Settings - Conventional
Thermostat (non-communicating)
This furnace is equipped with a two-stage, variable speed
integrated control. This control manages ignition timing,
heating mode fan off delays and indoor blower speeds based
on selections made using the control dip switches and
jumpers. The control includes an internal watchguard
feature which automatically resets the ignition control when
it has been locked out. After one hour of continuous
thermostat demand for heat, the watchguard will break and
remake thermostat demand to the furnace and automatically
reset the control to relight the furnace.
NOTE:
All Comfort Sync™ settings are set at the Comfort
Sync™ thermostat. See Comfort Sync™ installation
instruction. In Comfort Sync™ communication system all
DIP switch and clippable link settings are ignored. For
conventional thermostats proceed with DIP switch and
clippable link settings as outlined in the following.
Heating Operation DIP Switch Settings
Switch 1 - Thermostat Selection —
This unit may be used
with either a single-stage or two-stage thermostat. The
thermostat selection is made using a DIP switch which must
be properly positioned for the particular application. The
DIP switch is factory-positioned for use with a two-stage
thermostat. If a single-stage thermostat is to be used, the
DIP switch must be repositioned.
Select “OFF”
for two-stage heating operation controlled
by a two-stage heating thermostat (factory setting);
Select “ON”
for two-stage heating operation controlled
by a single-stage heating thermostat. This setting
provides a timed delay before second-stage heat
is initiated.
Switch 2 — Second Stage Delay
(Used with Single-Stage Thermostat Only) —
This switch
is used to determine the second stage on delay when a
single-stage thermostat is being used. The switch is factory-
set in the OFF position, which provides a 7-minute delay
before second-stage heat is initiated. If the switch is toggled
to the ON position, it will provide a 12-minute delay before
second-stage heat is initiated. This switch is only activated
when the thermostat selector jumper is positioned for
SINGLE- stage thermostat use.
Switches 3 and 4 — Blower-Off Delay —
The blower-ON
delay of 30 seconds is not adjustable. The blower OFF
delay (time that the blower operates after the heating
demand has been satisfied) can be adjusted by moving
switches 3 and 4 on the integrated control. The unit is
shipped from the factory with a blower-OFF delay of 90
seconds. The blower OFF delay affects comfort and is
adjustable to satisfy individual applications. Adjust the
blower OFF delay to achieve a supply air temperature
between 90° and 110°F at the exact moment that the blower
is de-energized. Longer OFF delay settings provide lower
supply air temperatures; shorter settings provide higher
supply air temperatures. Table 14 provides the blower OFF
timings that will result from differentswitch settings.
Table 14
Blower OFF Delay Switch Settings
B lo w er O ff D elay
S w itch
3
S w itch 4
(S eco n d s)
60
O n
O ff
90 (F ac tory)
O ff
O ff
120
O ff
O n
180
O n
O n
Indoor Blower Operation DIP Switch Settings
Switches 5 and 6 — Cooling Mode Blower Speed
The unit is shipped from the factory with the dip switches
positioned for high speed (4) indoor blower motor operation
during the cooling mode. Table 15 provides the cooling
mode blower speeds that will result from different switch
settings. Switches 5 and 6 set the blower cfm for second-
stage cool. The integrated control automatically ramps down
to 70% of the second-stage cfm for first-stage cfm. Refer
to tables for corresponding cfm values.
Cooling Mode Blower Speeds
Table 15
S p ee d
S w itch 5
S w itch 6
Low
O n
O n
M edium Lo w
O ff
O n
M edium H igh
O n
O ff
H iqh (F ac tory)
O ff
O ff
Switches 7 and 8 — Cooling Blower Speed Adjustment
The unit is shipped from the factory with the dip switches
positioned for NORMAL (no) adjustment. The dip switches
may be positioned to adjust the blower speed by +10% or
-10% to better suit the application. Table 16 below provides
blower speed adjustments that will result from different
switch settings. Refer to tables for corresponding cfm
values.
Cooling Blower Speed Adjustment
Table 16
A d ju stm en t
S w itch 7
S w itch 8
+ 10% (ap pro x.)
O n
O ff
F ac tory D efault
O ff
O ff
-10% (appro x.)
O ff
O n
S
wi
tches 9 and 10 — Cooling Mode Blower Speed
Ramping —
Blower speed ramping may be used to
enhance dehumidification performance. The switches are
factory set at option A which has the greatest effect on
dehumidification performance. Table 17 provides the
cooling mode blower speed ramping options that will result
from different switch settings. The cooling mode blower
speed ramping options are detailed on the next page.
NOTE:
The off portion of the selected ramp profile also
applies during heat pump operation in dual fuel applications.
Содержание A80DS2V
Страница 3: ...506892 01 Page 3 of 64 Issue 1251 EXPANDED VIEW Figure 1...
Страница 24: ...506892 01 Page 24 of 64 Issue 1251 Figure 22...
Страница 25: ...506892 01 Page 25 of 64 Issue 1251 Figure 23 Optional Accessories for use with any Comfort SyncTM System...
Страница 28: ...506892 01 Page 28 of 64 Issue 1251 Table 13C Field Wiring Applications with Conventional Thermostat continued...
Страница 29: ...506892 01 Page 29 of 64 Issue 1251 Field Wiring Applications with Conventional Thermostat continued Table 13D...
Страница 30: ...506892 01 Page 30 of 64 Issue 1251 Figure 24 A80DS2V Schematic Wiring Diagram...
Страница 31: ...506892 01 Page 31 of 64 Issue 1251 Typical A80DS2V Field Wiring Diagram Figure 25...
Страница 32: ...506892 01 Page 32 of 64 Issue 1251 Integrated Control Figure 26...
Страница 50: ...506892 01 Page 50 of 64 Issue 1251 Integrated Control Diagnostic Codes...
Страница 51: ...506892 01 Page 51 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Страница 52: ...506892 01 Page 52 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Страница 53: ...506892 01 Page 53 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Страница 54: ...506892 01 Page 54 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Страница 55: ...506892 01 Page 55 of 64 Issue 1251 Program Unit Capacity Size Mode...
Страница 56: ...506892 01 Page 56 of 64 Issue 1251 Troubleshooting Heating Sequence of Operation...
Страница 57: ...506892 01 Page 57 of 64 Issue 1251 Troubleshooting Heat Sequence of Operation continued...
Страница 58: ...506892 01 Page 58 of 64 Issue 1251 Troubleshooting Heat Sequence of Operation continued...
Страница 59: ...506892 01 Page 59 of 64 Issue 1251 Troubleshooting Heat Sequence of Operation continued...
Страница 60: ...506892 01 Page 60 of 64 Issue 1251 Troubleshooting Continuous Fan Sequence of Operation...
Страница 61: ...506892 01 Page 61 of 64 Issue 1251 Start Up Performance Check List UNIT SET UP...
Страница 62: ...506892 01 Page 62 of 64 Issue 1251 Start Up Performance Check List continued...