8. The common vent diameter must always be at least as
large as the largest vent connector diameter.
19. In no case, shall the vent connector be sized more than
two consecutive table size diameters over the size of
the draft hood outlet or flue collar outlet.
20. Do not install a manual damper, barometric draft
regulator or flue restrictor between the furnace and the
chimney.
21. When connecting this appliance to an existing dedicated
or common venting system, you must inspect the venting
system’s general condition and look for signs of
corrosion. The existing vent pipe size must conform to
these instructions and the provided venting tables. If
the existing venting system does not meet these
requirements, it must be resized.
Table 5
Capacity of Type B Double Wall Vents with Type B Double Wall Connectors
Serving a Single Category I Appliance
NOTE:
Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent
configurations, the vent system is assumed to have two 90 ° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal
one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Содержание A80DS2V
Страница 3: ...506892 01 Page 3 of 64 Issue 1251 EXPANDED VIEW Figure 1...
Страница 24: ...506892 01 Page 24 of 64 Issue 1251 Figure 22...
Страница 25: ...506892 01 Page 25 of 64 Issue 1251 Figure 23 Optional Accessories for use with any Comfort SyncTM System...
Страница 28: ...506892 01 Page 28 of 64 Issue 1251 Table 13C Field Wiring Applications with Conventional Thermostat continued...
Страница 29: ...506892 01 Page 29 of 64 Issue 1251 Field Wiring Applications with Conventional Thermostat continued Table 13D...
Страница 30: ...506892 01 Page 30 of 64 Issue 1251 Figure 24 A80DS2V Schematic Wiring Diagram...
Страница 31: ...506892 01 Page 31 of 64 Issue 1251 Typical A80DS2V Field Wiring Diagram Figure 25...
Страница 32: ...506892 01 Page 32 of 64 Issue 1251 Integrated Control Figure 26...
Страница 50: ...506892 01 Page 50 of 64 Issue 1251 Integrated Control Diagnostic Codes...
Страница 51: ...506892 01 Page 51 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Страница 52: ...506892 01 Page 52 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Страница 53: ...506892 01 Page 53 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Страница 54: ...506892 01 Page 54 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Страница 55: ...506892 01 Page 55 of 64 Issue 1251 Program Unit Capacity Size Mode...
Страница 56: ...506892 01 Page 56 of 64 Issue 1251 Troubleshooting Heating Sequence of Operation...
Страница 57: ...506892 01 Page 57 of 64 Issue 1251 Troubleshooting Heat Sequence of Operation continued...
Страница 58: ...506892 01 Page 58 of 64 Issue 1251 Troubleshooting Heat Sequence of Operation continued...
Страница 59: ...506892 01 Page 59 of 64 Issue 1251 Troubleshooting Heat Sequence of Operation continued...
Страница 60: ...506892 01 Page 60 of 64 Issue 1251 Troubleshooting Continuous Fan Sequence of Operation...
Страница 61: ...506892 01 Page 61 of 64 Issue 1251 Start Up Performance Check List UNIT SET UP...
Страница 62: ...506892 01 Page 62 of 64 Issue 1251 Start Up Performance Check List continued...