Replacement Considerations with CompactLogix and Compact GuardLogix Systems
Chapter 3
The items that are highlighted in this table are where 5370 and older
controllers and the 5380 controllers behavior differ.
Because the 5370 and 5380 controllers have 32-bit data integrity, this only
applies to data structures larger than 32 bits. If word-level integrity is your
primary concern, the 32-bit data integrity does not impact your data use.
Good programming practice dictates the use of two unique words at the
beginning and the end of data. The controller validates the words to assure the
entire structure has data integrity. We recommend that the handshake data is
changed and the application code validates it every transaction before the
controller application code or higher-level system reading controller data acts
on it.
Table 13 - Behavior Differences
Tag Read/
Write Source
Tag Access
UID/UIE
CPS
Periodic Task
5380 Controllers
5370 Controllers
5380 Controllers
5370 Controllers
5380 Controllers
5370 Controllers
HMI
Allows
Blocks
Blocks
Blocks
Allows
Blocks
MSG
Allows
Blocks
Blocks
Blocks
Allows
Blocks
I/O Update
Allows
Allows
Blocks
Blocks
Allows
Allows
Produce/
Consume
Allows
Allows
Blocks
Blocks
Allows
Allows
Other User
Tasks
Blocks
Blocks
Blocks
Blocks
Allows
Allows
Motion
Planner
Allows
Allows
Blocks
Blocks
Allows
Allows
Blocks - Prevents source data values from change by communications during application execution.
Allows - Communications can change source data values during application execution.