152
Rockwell Automation Publication 1756-RM100F-EN-P - October 2018
Chapter 8
Diagnostics and Status Indicators with CompactLogix Systems
Controller Status Indicators
The controller status indicators on the 5380 controllers are the same as the
controller status indicators on the 5370 controllers. The controller status
indicators include the following:
• RUN
• FORCE
• OK
• SD
Controller status indicators function the same on 5380 and 5370 controllers.
DNS Invalid
The DNS used in the port IP configuration is not valid.
No Project
No project is loaded on the controller.
To load a project, complete one of the following tasks:
• Use the Studio 5000 Logix Designer® application to download the project to the controller
• Use an SD card to load a project to the controller
Project Name
The name of the project that is loaded on the controller.
BUSY
The I/O modules that are associated with the controller are not yet fully powered.
Let powerup and I/O module self-testing complete.
Corrupt Certificate Received
The security certificate that is associated with the firmware is corrupted.
Go to
http://www.rockwellautomation.com/support/
and download the firmware revision to which you are trying to update. Replace the
firmware revision that you have previously installed with that posted on the Technical Support website.
Corrupt Image Received
The firmware file is corrupted.
Go to
http://www.rockwellautomation.com/support/
and download the firmware revision to which you are trying to update. Replace the
firmware revision that you have previously installed with that posted on the Technical Support website.
Backup Energy HW Failure - Save Project
A failure with the embedded storage module has occurred. If a power is lost to the controller, the controller cannot save the program. If
you see this message, save your program to the SD card before you remove power and replace the controller.
Backup Energy Low - Save Project
The embedded storage module does not have sufficient energy to enable the controller to save the program if power is lost to the
controller. If you see this message, save your program to the SD card before you remove power and replace the controller.
Flash in Progress
A firmware update that is initiated via ControlFLASH™, ControlFLASH Plus™, or AutoFlash utilities is in progress.
Let the firmware update complete without interruption.
Firmware Installation Required
The controller currently uses boot firmware, that is, revision 1.
xxx
, and requires a firmware update.
SD Card Locked
An SD card that is locked is installed.
Table 21 - General Status Messages (continued)
Message
Interpretation
Содержание Studio 5000 Logix Emulate
Страница 8: ...8 Rockwell Automation Publication 1756 RM100F EN P October 2018 Table of Contents Notes...
Страница 16: ...16 Rockwell Automation Publication 1756 RM100F EN P October 2018 Chapter 1 BeforeYou Begin a Migration Notes...
Страница 170: ...170 Rockwell Automation Publication 1756 RM100F EN P October 2018 Index Notes...
Страница 171: ......