Rockwell Automation Publication 1756-RM100F-EN-P - October 2018
151
Diagnostics and Status Indicators with CompactLogix Systems
Chapter 8
UPDT
A firmware update is being conducted from the SD card upon powerup.
If you do not want the firmware to update upon powerup, change the Load Image property of the controller.
Rev
XX
.
xxx
The firmware major and minor revision of the controller.
5069-L3xxx
The controller catalog number and series.
Link A
x
Down
Message appears when an Ethernet port does not have a network connection. Message scrolls continuously during operation.
IMPORTANT
: When the controller operates in Dual-IP mode, this information is provided for each link, that is, Link A1 and Link A2. The
link name appears before the information.
Link A
x
Disabled
Message appears when you have disabled an Ethernet port. Message scrolls continuously during operation.
IMPORTANT
: When the controller operates in Dual-IP mode, this information is provided for each link, that is, Link A1 and Link A2. The
link name appears before the information.
DHCP- 00:00:XX:XX:XX:XX
Message appears when the controller is set for DHCP, but not configured on a network. The message shows the MAC address of the
controller. Message scrolls continuously during operation if no IP address is set.
IMPORTANT
: When the controller operates in Dual-IP mode, this information is provided for each port, that is, Port A1 and Port A2.
The port name appears before the information.
Ethernet Port Rate/Duplex State
The current port rate and duplex state when an Ethernet port has a connection. Message scrolls continuously during operation.
IMPORTANT
: When the controller operates in Dual-IP mode, this information is provided for each link, that is, Link A1 and Link A2. The
link name appears before the information.
IP Address
The IP address of the controller. Appears on powerup and scrolls continuously during operation. If the IP address is not yet set, the MAC
address appears.
IMPORTANT
: When the controller operates in Dual-IP mode, this information is provided for each port, that is, Port A1 and Port A2.
The port name appears before the information.
Duplicate IP - 00:00:XX:XX:XX:XX
Message appears when the controller detects a device with the same IP Address on the network. The message shows the MAC address
of the device with the duplicate IP Address. Message scrolls continuously during operation.
IMPORTANT
: When the controller operates in Dual-IP mode, this information is provided for each port, that is, Port A1 and Port A2.
The port name appears before the information.
DHCP-Address Lost
The controller has communicated with the DHCP server to renew the IP address. The server either did not reply or did not renew the IP
address.
The controller continues to operate, but with no Ethernet connectivity out of this port.
IMPORTANT
: When the controller operates in Dual-IP mode, this information is provided for each port, that is, Port A1 and Port A2.
The port name appears before the information.
IP Address/Mask/Gateway/DNS Invalid
The DHCP server responded with an unusable combination.
IMPORTANT
: When the controller operates in Dual-IP mode, this information is provided for each port, that is, Port A1 and Port A2.
The port name appears before the information.
IP Address Invalid
The IP address that is used in the port configuration is not valid.
IMPORTANT
: When the controller operates in Dual-IP mode, this information is provided for each port, that is, Port A1 and Port A2.
The port name appears before the information.
Mask Invalid
The Subnet/Network Mask used in the port configuration is not valid.
IMPORTANT
: When the controller operates in Dual-IP mode, this information is provided for each port, that is, Port A1 and Port A2.
The port name appears before the information.
Gateway Invalid
The Gateway address that is used in the port IP configuration is not valid.
IMPORTANT
: When the controller operates in Dual-IP mode, this information is provided for each port, that is, Port A1 and Port A2.
The port name appears before the information.
Table 21 - General Status Messages (continued)
Message
Interpretation
Содержание Studio 5000 Logix Emulate
Страница 8: ...8 Rockwell Automation Publication 1756 RM100F EN P October 2018 Table of Contents Notes...
Страница 16: ...16 Rockwell Automation Publication 1756 RM100F EN P October 2018 Chapter 1 BeforeYou Begin a Migration Notes...
Страница 170: ...170 Rockwell Automation Publication 1756 RM100F EN P October 2018 Index Notes...
Страница 171: ......