Table 8 - Technical Specifications
Attribute
CompactLogix 5370 L3 Controller
CompactLogix 5380 Controller
Memory
1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM: 1 MB
1769-L33ER, 1769-L33ERM: 2 MB
1769-L36ERM: 3 MB
1769-L37ERM: 4 MB
1769-L38ERM: 5 MB
5069-L306ER, 5069-L306ERM: 0.6 MB
5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM: 1 MB
5069-L320ER, 5069-L320ERM: 2 MB
5069-L330ER, 5069-L330ERM: 3 MB
5069-L340ER, 5069-L340ERM: 4 MB
5069-L350ERM: 5 MB
5069-L380ERM: 8 MB
5069-L3100ERM: 10 MB
Local I/O modules supported
1769 Compact I/O™ only
Number of local I/O modules that are supported varies by controller
catalog number
Compact 5000 I/O Standard modules only
Number of local I/O modules that are supported varies by
controller catalog number
Embedded Ethernet
10/100 Mbps
10/100/1000 Mbps
Ethernet nodes
1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM: 16
1769-L33ER, 1769-L33ERM: 32
1769-L36ERM: 48
1769-L37ERM: 64
1769-L38ERM: 80
5069-L306ER, 5069-L306ERM: 16
5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM: 24
5069-L320ER, 5069-L320ERM: 40
5069-L330ER, 5069-L330ERM: 60
5069-L340ER, 5069-L340ERM: 90
5069-L350ERM: 120
5069-L380ERM: 150
5069-L3100ERM: 180
Ethernet performance
Ethernet I/O (Class 0/1): 10,000 packets per second max
Ethernet Messaging (Class 3): 400 packets per second max
Ethernet I/O (Class 0/1): 128,000 packets per second
Ethernet Messaging (Class 3): 2000 messages per second
(2)
Dual-IP mode
Not supported
Supported with the Logix Designer application, version 29
or later
Unconnected message buffers
No fixed limits, as long as the controller can allocate the buffer at
will.
320 - Any combination of outbound and inbound messages
Concurrent cached message instructions
in the running state
32, drawn from the 250 total connections supported by the
controller.
256 dedicated buffers
HMI and Messaging (Class 3)
Drawn from the 250 total connections supported by the controller.
512 dedicated messages (256 incoming messages and 256
outgoing messages)
Integrated motion
EtherNet/IP network
Motion axes
1769-L30ERM - As many as 4 axes
1769-L33ERM- As many as 8 axes
1769-L36ERM, 1769-L37ERM, 1769-L38ERM - As many as 16 axes
Any combination of these supported axis types:
• CIP™
• Consumed
• Virtual
• Position loop drives
5069-L306ERM: As many as 2 axes
5069-L310ERM: As many as 4 axes
5069-L320ERM: As many as 8 axes
5069-L330ERM: As many as 16 axes
5069-L340ERM: As many as 20 axes
5069-L350ERM: As many as 24 axes
5069-L380ERM: As many as 28 axes
5069-L3100ERM: As many as 32 axes
Any combination of these supported axis types:
• CIP
• Consumed
• Virtual
• Position loop drives
Axes/ms over EtherNet/IP™ port
As many as 2 (2 ms coarse update period and 50% controller load)
IMPORTANT
: Not all CompactLogix 5370 controllers support
Integrated Motion over an EtherNet/IP network.
As many as 32 when you use the built-in EtherNet/IP port at
1 Gbps
IMPORTANT
: Not all CompactLogix 5380 controllers support
Integrated Motion over an EtherNet/IP network.
Содержание Studio 5000 Logix Emulate
Страница 8: ...8 Rockwell Automation Publication 1756 RM100F EN P October 2018 Table of Contents Notes...
Страница 16: ...16 Rockwell Automation Publication 1756 RM100F EN P October 2018 Chapter 1 BeforeYou Begin a Migration Notes...
Страница 170: ...170 Rockwell Automation Publication 1756 RM100F EN P October 2018 Index Notes...
Страница 171: ......