Chapter 4
Preliminary Operating Considerations
4–10
The fastest module update time occurs when only one channel with a 250 Hz
filter frequency is enabled.
Module Update Time = 17 ms
NOTE: With 3 channels enabled, the module update time is:
3 channels
17 ms/channel = 51 ms
The slowest module update time occurs when four channels, each using a 10
Hz filter frequency, are enabled.
Module Update Time = 4
305 ms = 1220 ms
Figure 4.6
Scanning Cycle
Wait for Channel 0 A/D Conversion
Read Channel 0 A/D
Wait for Channel 1 A/D Conversion
Read Channel 1 A/D
Configure and Start Channel 0 A/D
Start
Configure and Start Channel 1 A/D
Calculate Channel 1 Data
Channel 0
Channel 1
Scan Cycle With Channels 0 & 1 Enabled Only
Calculate Channel 0 Data
Update Channel 0 Data Word
Update Channel 1 Data Word