Appendix
B
B–1
RTD Standards
The following table shows various international and local RTD standards that
apply to the 1746–NR4:
RTD Type
α
➀
IEC
➁
DIN
➂
D100
➃
SAMA
➄
JIS (old)
➅
JIS (new)
➆
Minco
➇
100
W
Platinum
0.00385
X
X
X
200
W
Platinum
0.00385
X
X
X
500
W
Platinum
0.00385
X
X
X
1000
W
Platinum
0.00385
X
X
X
100
W
Platinum
0.03916
X
X
200
W
Platinum
0.03916
X
X
500
W
Platinum
0.03916
X
X
1000
W
Platinum
0.03916
X
X
10
W
Copper
➈
0.00426
X
120
W
Nickel
➉
0.00618
X
120
W
Nickel
0.00672
X
604
W
Nickel Iron
0.00518
X
➀
α
is the temperature coefficient of resistance which is defined as the resistance change per ohm per
°
C.
➁
International Electrotechnical Commission Standard 751–1983
➂
German Standard, DIN 43760–1980 and DIN 43760–1987
➃
U.S. Standard D100
➄
Scientific Apparatus Makers Association Standard RC21–4–1966
➅
Japanese Industrial
Standard JIS C1604–1981
➆
Japanese Standard JIS C1604–1989
➇
Minco Type ‘NA’ (Nickel) and Minco Type ‘FA’ (Nickel–Iron)
➈
Actual value at 0
°
C is 9.042
W
per SAMA standard RC21–4–1966.
➉
Actual value at 0
°
C is 100
W
per DIN standard.
!
ATTENTION: We recommend you use RTDs that conform to
the standards in the table above. Failure to heed this caution may
result in reduced accuracy of the RTD system.
Содержание SLC 500 1746-NR4
Страница 1: ...User Manual SLC 500t RTD Resistance Input Module Cat No 1746 NR4 Allen Bradley AB Spares ...
Страница 15: ...Preface P 8 Notes AB Spares ...
Страница 37: ...Chapter 2 Quick Start 2 12 Notes AB Spares ...
Страница 63: ...Chapter 4 Preliminary Operating Considerations 4 12 Notes AB Spares ...
Страница 87: ...Chapter 5 Channel Configuration Data and Status 5 24 Notes AB Spares ...
Страница 107: ...Chapter 7 Module Diagnostics and Troubleshooting 7 8 Notes AB Spares ...
Страница 117: ...Chapter 8 Application Examples 8 10 Notes AB Spares ...
Страница 123: ...Appendix A Specifications A 6 Notes AB Spares ...
Страница 125: ...Appendix B RTD Standards B 2 Notes AB Spares ...