Appendix C
NR4 Configuration Worksheet
C–3
8. If you have selected scaled–for–PID or proportional counts data formats,
you can choose module defined scaling (this applies the scale associated
with your data format selection in step 2). In addition, use bits 13 and 14
if you want to define the scaling range yourself for proportional counts
data format (user–set scaling). If you choose to define the scaling range
for proportional counts, make sure to enter the lower and upper user–set
limits in words 4 and 5 (defines range 0) or 6 and 7 (defines range 1).
Refer to chapter 5.
Bits
13 and 14
Select
Scaling
00 = module defined scaling
01 = configuration words 4 and 5 used for scaling (range 0)
10 = configuration words 6 and 7 used for scaling (range 1)
11 = not used (invalid setting)
9. Make sure a zero is in bit 15. This bit is not used.
10.Build the channel configuration word for every channel that is being used
on each RTD module repeating the procedures given in steps 1–9.
11. Enter the completed configuration words for each module into the
summary worksheet on the following page.
12.Following the steps outlined in chapter 6, Ladder Programming
Examples, enter this configuration data into your ladder program and
copy it to the RTD module.
Содержание SLC 500 1746-NR4
Страница 1: ...User Manual SLC 500t RTD Resistance Input Module Cat No 1746 NR4 Allen Bradley AB Spares ...
Страница 15: ...Preface P 8 Notes AB Spares ...
Страница 37: ...Chapter 2 Quick Start 2 12 Notes AB Spares ...
Страница 63: ...Chapter 4 Preliminary Operating Considerations 4 12 Notes AB Spares ...
Страница 87: ...Chapter 5 Channel Configuration Data and Status 5 24 Notes AB Spares ...
Страница 107: ...Chapter 7 Module Diagnostics and Troubleshooting 7 8 Notes AB Spares ...
Страница 117: ...Chapter 8 Application Examples 8 10 Notes AB Spares ...
Страница 123: ...Appendix A Specifications A 6 Notes AB Spares ...
Страница 125: ...Appendix B RTD Standards B 2 Notes AB Spares ...