Rockwell Automation Publication 20B-IN019E-EN-P - July 2013
45
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Drive Identification
Refer to the drive nameplate and locate
the “Voltage Code,” “Current Rating,”
“Frame,” and “UL Type” (Frames 5…6).
Use this information to locate the
proper procedure in the following
tables.
Jumper Settings and Locations
Cat No. 20B
D xxx
x x xxxxxxx
Made in the USA (TAC 1J)
Rockwell Automation, Mequon WI 53092-4400
UL TYPE 1/IP20
Mfd. in 2007 on Aug 1
Frame:
3
Serial Number: xxxxxxx
Series: B
I/O: 24VAC/DC (Standard)
Original Firmware V. x.xxx
Listed
Ind. Cont
Eq. 966X
U
c
US
L
®
Normal Duty Power
Heavy Duty Power
AC Voltage Range
Amps
Input: 3 Phase, 47-63Hz
Output: 3 Phase, 0-400 Hz
AC Voltage Range
Base Hz (default)
Continuous Amps
1 Min Overload Amps
3 Sec Overload Amps
xxx kW
xxx kW
342-440
xxx
0-400
50 Hz
xxx
xxx
xxx
xxx kW
xxx kW
432-528
xxx
400V
480V
0-460
60 Hz
xxx
xxx
xxx
N223
Voltage Code
Frame
Current Rating
UL Type
Series
Fram
e
Vo
lt
ag
e
Code
Cu
rrent
Ra
ti
ng
Factory Default Jumper Settings
Power Source Type
MOV/Input
Filter Caps
DC Bus Common
Mode Caps
0…1
All Drives
B…E
All
PE_B
Installed
PE_A
Installed
Solid Ground
• Remove the I/O Cassette (see
page 53
). Verify
that jumpers are installed at the “PE_A” and
“PE_B” locations on the Power Board.
Non-Solid Ground
• Remove the I/O Cassette (see
page 53
).
Remove jumpers at the “PE_A” and “PE_B”
locations on the Power Board.
2
B…E
All
PE_MOV
Installed
PE_CAP
Installed
Solid Ground
• Verify that jumpers are installed at the
“PE_CAP” and “PE_MOV” locations.
Non-Solid Ground
• Remove jumpers at the “PE_CAP” and
“PE_MOV” locations.
BR1
BR2
DC+
DC–
PE
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Use 75C
Wir
e O
nly
#10-#14 A
WG
Tor
que t
o 7 in-lbs
!
DANGER
PE A
PE B
CM Cap
MOV
BR1 BR2 DC+ DC- U/T1 V/T2 W/T3
SHLD
SHLD
PE R/L1 S/L2 T/L3
PE 2
MOV-PE JMPR
PE 1
AUX IN+ AUX OUT–
75C Cu Wire
6 AWG [10MM
2
] Max.
12 IN. LBS.
1.4 N-M
} TORQUE
WIRE
STRIP
CONTROL
PO
WER
PE 4
PE 3
MOV
PE_MOV
CM Cap
PE_CAP