Rockwell Automation Publication 20P-TG001C-EN-P - February 2018
83
Part Replacement Procedures
Chapter 3
AC Current Transducers on Drives with Bus Bars
6. Remove the power connections from terminals U and V at the bottom
of the drive.
7. Remove the M4 x12.5 mm screws and washers that secure each of the
AC current transducers to the U and V Phase terminal bus bars.
IMPORTANT
Mark all connections and wires before removal to avoid incorrect wiring
during reassembly.
7
U Phase bus bar
V Phase bus bar
Tightening torque:
3.0 N•m (26.5 lb•in)