Rockwell Automation Publication 20P-TG001C-EN-P - February 2018
75
Part Replacement Procedures
Chapter 3
Sizing Resistor Configuration
Use
to determine the correct resistor configuration on
the pulse transformer board for your drive size. The tables use these
conventions:
• A resistance value in a cell indicates that the resistor must be left on the
board
• “Remove” in a cell indicates that the resistor must be cut off the board
• “-” indicates that there is no resistor in that location on the board
Table 14 - 230V AC Input Drives
Table 15 - 460V AC Input Drives
Drive Current
Rating Code
DC
Amps
AC Line
Amps
Hp
R1
R2
R3
R4
R5
7P0
7
5.7
1.5
Remove
27.4 Ω
Remove
Remove
–
9P0
9
7.4
2
Remove
Remove
39.2 Ω
Remove
–
012
12
9.8
3
Remove
27.4 Ω
Remove
Remove
–
020
20
16
5
56.2 Ω
Remove
Remove
Remove
–
029
29
24
7.5
Remove
Remove
39.2 Ω
Remove
–
038
38
31
10
Remove
27.4 Ω
Remove
Remove
–
055
55
45
15
56.2 Ω
27.4 Ω
Remove
Remove
–
073
73
60
20
Remove
27.4 Ω
39.2 Ω
Remove
–
093
93
76
25
Remove
Remove
Remove
6.98 Ω
–
110
110
90
30
Remove
Remove
Remove
6.98 Ω
–
Drive Current
Rating Code
DC
Amps
AC Line
Amps
Hp
R1
R2
R3
R4
R5
4P1
4.1
3.3
2
56.2 Ω
Remove
Remove
Remove
–
6P0
6
4.9
3
Remove
Remove
39.2 Ω
Remove
–
010
10
8.2
5
Remove
Remove
39.2 Ω
Remove
–
014
14
11.4
7.5
Remove
27.4 Ω
Remove
Remove
–
019
19
15.5
10
56.2 Ω
Remove
Remove
Remove
–
027
27
22.1
15
Remove
Remove
39.2 Ω
Remove
–
035
35
28.6
20
Remove
27.4 Ω
Remove
Remove
–
045
45
36.8
25
56.2 Ω
Remove
39.2 Ω
Remove
–
052
52
42.5
30
56.2 Ω
27.4 Ω
Remove
Remove
–
073
73
59.6
40
Remove
27.4 Ω
39.2 Ω
Remove
–
086
86
70.3
50
Remove
Remove
Remove
6.98 Ω
–
100
100
81.7
60
Remove
Remove
Remove
6.98 Ω
–
129
129
105.4
75
Remove
Remove
Remove
6.98 Ω
–