Communication and I/O Table Mapping
4-3
This section describes how the adapter handles the following services:
•
Set_Parameter
•
Check_Configuration
•
Get_Configuration
•
Data_Exchange
•
Global_Command
•
Slave_Diagnostic
Set_Parameter
The master uses this service to identify itself with the adapter and to
specify how the adapter is to operate. Set_parameter data is
comprised of a series of octets (maximum of 244). Octet 0-6 is defined
in the DIN 19245-3 standard, while octet 7-243 contain specific
information for the adapter itself (referred to as User Parameter Data).
The module configuration you previously selected is passed on to the
adapter and I/O modules via the User Parameter data.
User Parameter Data
Octet 7 in the parameter data is reserved for the Profibus-DP ASIC
onboard and must equal 00h.
Beginning at octet 8, each configured module allocates a minimum of
three bytes of user parameter data as shown in the following table.
The first two bytes define the product code for the installed module,
the third byte defines the control byte followed by configuration data
(if used).
Octet
Value
Description
0
-
Station Status (see DIN 19245-3)
1
1-255
Watchdog Factor 1
2
1-255
Watchdog Factor 2
3
0-255
Minimum Station Delay (TSDR)
4
4
Vendor (High byte)
5
239
Vendor (Low byte)
6
-
Group Identification (see DIN 19245-3)
7-243
See below
User Parameter Data
Содержание POINT I/O PROFIBUS 1734-APB
Страница 1: ...POINT I O PROFIBUS Adapter Module Cat No 1734 APB User Manual Allen Bradley HMIs...
Страница 6: ...Publication 1734 UM005B EN P June 2001 Preface 4...
Страница 24: ...Publication 1734 UM005B EN P June 2001 2 10 Installing the PROFIBUS Adapter...
Страница 62: ...Publication 1734 UM005B EN P June 2001 6 4 Troubleshooting the PROFIBUS Adapter...
Страница 82: ...Publication 1734 UM005B EN P June 2001 B 18 Default Data Maps...
Страница 84: ...Publication 1734 UM005B EN P June 2001 2...
Страница 87: ...Allen Bradley HMIs...