Publication 1734-UM005B-EN-P - June 2001
2-8
Installing the PROFIBUS Adapter
Wiring Connections
Proceed as follows. Make all connections to the removable terminal
block (RTB).
1.
Connect chassis ground to terminal 2.
2.
Connect 12/24V supply positive lead to terminal 6.
3.
Connect 12/24V negative lead to terminal 4.
External power applied across terminal 6 (+) and 5 (-) connects
to the internal power bus.
Do not connect anything to terminals 0 and 1. These are
reserved terminals.
4.
Connect the PROFIBUS connector plug to the D-shell on the
adapter. Tighten the screws to secure.
Terminal
Description
Notes
0
No connection
Reserved
1
No connection
2
Chassis Ground
3
Chassis Ground
4
Common
5
Common
6
Voltage Input
Apply 12/24V dc. Connects to
the internal power bus.
7
Voltage Input
CHAS GND
NC
NC
C
V
CHAS GND
V dc
C
V
0
2
4
6
1
3
5
7
This dc supply will be
connected to the
internal power bus.
12/24V dc
Do not connect 120/240V ac
power to this supply.
NC = No Connection
CHAS GND = Chassis Ground
C = Common
V = Supply
Содержание POINT I/O PROFIBUS 1734-APB
Страница 1: ...POINT I O PROFIBUS Adapter Module Cat No 1734 APB User Manual Allen Bradley HMIs...
Страница 6: ...Publication 1734 UM005B EN P June 2001 Preface 4...
Страница 24: ...Publication 1734 UM005B EN P June 2001 2 10 Installing the PROFIBUS Adapter...
Страница 62: ...Publication 1734 UM005B EN P June 2001 6 4 Troubleshooting the PROFIBUS Adapter...
Страница 82: ...Publication 1734 UM005B EN P June 2001 B 18 Default Data Maps...
Страница 84: ...Publication 1734 UM005B EN P June 2001 2...
Страница 87: ...Allen Bradley HMIs...