Rockwell Automation Publication 1734-IN043B-EN-E - January 2019
5
POINT I/O 4 Channel IO-Link Master Module
Special Conditions for Safe Use
ATTENTION:
• This product is grounded through the DIN rail to chassis ground. Use zinc
plated chromate-passivated steel DIN rail to assure proper grounding. The use
of other DIN rail materials (for example, aluminum or plastic) that can corrode,
oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail
properly. Refer to Industrial Automation Wiring and Grounding Guidelines,
publication
1770-4.1
, for more information.
• Do not remove or replace an Adapter Module while power is applied.
Interruption of the backplane can result in unintentional operation or
machine motion.
• Do not discard the end cap. Use this end cap to cover the exposed
interconnections on the last mounting base on the DIN rail. Failure to do so
could result in equipment damage or injury from electric shock.
• If this equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
ATTENTION:
Do not wire more than two conductors on any single terminal.