22
Rockwell Automation Publication 1734-IN043B-EN-E - January 2019
POINT I/O 4 Channel IO-Link Master Module
On-state voltage, nom
24V DC
On-state voltage drop, max
0.9V DC
On-state current, max
150 mA
Off-state current leakage, max
0.5 mA
Module current (all outputs), max
600 mA
Surge current, max
0.3 A for 10 ms, repeatable every 3 s
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, operating cold),
IEC 60068-2-2 (Test Bd, operating dry heat),
IEC 60068-2-14 (Test Nb, operating thermal shock):
-20…+55 °C (-4…
+
131 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, unpackaged nonoperating cold),
IEC 60068-2-2 (Test Bb, unpackaged nonoperating dry heat),
IEC 60068-2-14 (Test Na, unpackaged nonoperating thermal shock):
-40…+85 °C (-40…+185 °F)
Temperature, surrounding air,
max
55 °C (131 °F)
Relative humidity
IEC 60068-2-30 (Test Db, unpackaged damp heat):
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, unpackaged shock):
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, unpackaged shock):
50 g
Emissions
IEC 61000-6-4
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
POINT I/O 4 Channel IO-Link Master Module 1734-4IOL – Standard Digital Output
Attribute
Value