24
Rockwell Automation Publication 2711P-UM006A-EN-P - November 2010
Chapter 2
Install Terminal
North American Hazardous
Location Approval
DC-powered terminals have a temperature code of T4 when operating in a
55 °C (131 °F) maximum ambient temperature. Do not install terminals in
environments where atmospheric gases have ignition temperatures less than
135 °C (275 °F).
The AC-powered terminals have a temperature code of T3 when operating in a
55 °C (131 °F) maximum ambient temperature. Do not install terminals in
environments where atmospheric gases have ignition temperatures less then
200 °C (392 °F).
The following information applies when operating this
equipment in hazardous locations.
Informations sur l’utilisation de cet équipement en
environnements dangereux.
When marked, these products are suitable for use in "Class I,
Division 2, Groups A, B, C, D"; Class I, Zone 2, Group IIC, Class II,
Division II, Groups F, G; Class III hazardous locations and
nonhazardous locations only. Each product is supplied with
markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within a
system, the most adverse temperature code (lowest "T" number)
may be used to help determine the overall temperature code of the
system. Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the time
of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent
qu'à une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque produit
est livré avec des marquages sur sa plaque d'identification qui
indiquent le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le
code de température global du système. Les combinaisons
d'équipements dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de l'installation.
WARNING: EXPLOSION HAZARD -
•
Do not disconnect equipment unless power
has been removed or the area is known to be
nonhazardous.
•
Do not disconnect connections to this
equipment unless power has been removed
or the area is known to be nonhazardous.
•
Substitution of components may impair
suitability for Class I, Division 2.
•
Peripheral equipment must be suitable for
the location in which it is used.
•
The battery or real-time clock module in this
product must only be changed in an area
known to be nonhazardous.
•
All wiring must be in accordance with Class
I, Division 2, Class II, Division 2, or Class III,
Division 2 wiring methods of Articles 501,
502 or 503, as appropriate, of the National
Electrical Code and/or in accordance with
Section 18-1J2 of the Canadian Electrical
Code, and in accordance with the authority
having jurisdiction.
AVERTISSEMENT: RISQUE D’EXPLOSION –
•
Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher l'équipement.
•
Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher les connecteurs. Fixer
tous les connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
•
La substitution de composants peut rendre
cet équipement inadapté à une utilisation en
environnement de Classe I, Division 2.
•
S'assurer que l'environnement est classé
non dangereux avant de changer les piles.
Содержание PanelView Plus 6 1000
Страница 10: ...10 Rockwell Automation Publication 2711P UM006A EN P November 2010 Preface Notes ...
Страница 32: ...32 Rockwell Automation Publication 2711P UM006A EN P November 2010 Chapter 2 Install Terminal Notes ...
Страница 100: ...100 Rockwell Automation Publication 2711P UM006A EN P November 2010 Chapter 5 Windows CE Operating System Notes ...
Страница 154: ...154 Rockwell Automation Publication 2711P UM006A EN P November 2010 Chapter 9 Troubleshoot the System Notes ...
Страница 158: ...158 Rockwell Automation Publication 2711P UM006A EN P November 2010 Appendix A Specifications Notes ...
Страница 167: ......