110
Rockwell Automation Publication 2711P-UM006A-EN-P - November 2010
Chapter 6
Install and Replace Components
6.
Locate the battery on the circuit board.
7.
Remove the battery by lifting up the side of the battery.
8.
Insert the new battery.
9.
Reattach the logic module by aligning the two connectors on the bottom
of the logic module with the connectors on the back of the display module.
10.
Push down on the logic module until it is firmly seated.
11.
Tighten the four captive screws that secure the logic module to a torque of
0.58 N•m (5…7 lb•in).
12.
Reattach the communication module, if necessary, and tighten the four
screws to a torque of 0.58 N•m (5…7 lb•in).
IMPORTANT
•
Use only replacement battery, catalog number 2711P-RY2032 ,or an
equivalent CR2032 lithium coin cell battery.
•
The battery may be removed for up to 15 seconds without losing the clock
and calendar data.
This product contains a hermetically sealed lithium battery which may need
to be replaced during the life of the product.
At the end of its life, the battery contained in this product should be collected
separately from any unsorted municipal waste.
The collection and recycling of batteries helps protect the environment and
contributes to the conservation of natural resources as valuable materials
are recovered.
Содержание PanelView Plus 6 1000
Страница 10: ...10 Rockwell Automation Publication 2711P UM006A EN P November 2010 Preface Notes ...
Страница 32: ...32 Rockwell Automation Publication 2711P UM006A EN P November 2010 Chapter 2 Install Terminal Notes ...
Страница 100: ...100 Rockwell Automation Publication 2711P UM006A EN P November 2010 Chapter 5 Windows CE Operating System Notes ...
Страница 154: ...154 Rockwell Automation Publication 2711P UM006A EN P November 2010 Chapter 9 Troubleshoot the System Notes ...
Страница 158: ...158 Rockwell Automation Publication 2711P UM006A EN P November 2010 Appendix A Specifications Notes ...
Страница 167: ......