Light Curtain Multi-Function Control Module User Manual

Or

i

g

i

nal 

i

nstruct

i

ons

Following connections may be used for test inputs.

Figure 12: Connection possibilities for the input

The timing of test input is as follows (Figure 13):

Table 12: Timing during testing

Figure 13: Test timing diagram (minimum off time = see configuration control document)

t

R

 means the max response time of the total system (see page 4). The 

machine controller has to check the output of the OSSD during such a 
test. If the machine controller detects an error, then the machine 
controller should not allow the machine to restart, respectively must stop 
the machine immediately. 

In case of a test failure the status output “Info2” will also provide a failure 
signal. 

Table 13

D

i

agnost

i

c

In the event of a fault condition, it will be indicated by

1. the red LED of a connected GuardShield Micro 400 safety light 

curtain are blinking

2. can be visually noticed in that the blue OptiLink LED (located on the 

side of a MSR42 unit) is off 

3. one of the info outputs (if configured) 

In this situation both safety outputs are low and the relays of the 
extension modules are open, and the controller unit is now in the so-
called lock-out mode.

Two options exist to leave the lock-out mode:

• Power up. If the fault is still present the controller will again show 

the lock-out mode.

• A start impulse longer than 10 s acts like a power up.

More detailed lock out information can be obtained with help of the 
USB/optical interface (445L-AF6150) and the software “Configuration 
& Diagnostic Tool”.

External 

f

aults

The following external faults apply to the “Out of Box” configurations 
only. Reference Table 14 for detailed information.

Table 14

Programmed Configuration Diagnostics can be obtained with the use of 
USB / Optical Interface (445l-AF6150) and the software 
“Configuration and Diagnostic Tool”

I

nternal 

f

aults

The following internal faults apply to the “Out of Box” configurations 
only. Reference Table 15 for detailed information.

Table 15

 

The lock-out mode of a MSR42 control module may be reset by one of 
two methods:

1. Power down, then Power up. If the fault is still present the module 

will again lock-out.

2. A start signal longer than 10 seconds acts like a power up.

Further diagnosis possibilities are possible with the software 
Configuration & Diagnostic Tool in combination with the USB/optical 
interface. If the MSR42 unit has a lock-out, the exact fault description 
can be determined with these tools. An exact description is available at 
any time after a lock-out, as long as the MSR42 unit is still in the lock-out 
condition.

Time

Value in ms

Response time to test signal

t

1

≤ t

R

ime to test

t

2

≤ t

1

Restart time after test

t

3

≥ t

R

Terminal

LED green

LED red

IN 1 or IN 2

External test signal high

External test signal low (test running)

short circuited

Test input

OSSD 1 / OSSD 2

open

t

1

t

2

t

3

No

Fault profile

Fault description

Measures & instructions

1

No power LED

No Power Connection to +24 
VDC OV

Check power connections and 
power supply

2

Light curtain LED(s) are 
flashing red

Light curtain Rx / Tx are swapped

Reverse Rx / Tx connections and 
retry

Open / missing light curtain 
cable

Replace expansion cable on the 
light curtain that is not flashing

Defect in light curtain

Replace light curtain

3

OSSD1 & OSSD2 LEDs are 
red
No relay outputs

Missing reset switch for manual 
reset

Add rest switch with N/O contact

Missing 24 VDC to GPIO3 and 
GPIO4 for automate reset.

Add 24VDC jumper to GPIO3 and 
GPIO4

Missing 24VDC to IN1 and IN2

Add 24VDC jumper to IN1 and 
IN2

No start release signal from 
external contactors

Check wiring and function of 
external contacts

No

Fault profile

Fault description

Measures & instructions

1

No Power LED

Power supply is ok but MSR42 
relay does not power up

Replace the MSR42 and retry

2

Relay is in Lockout mode
Will not initialize

All input and reset LEDS are ok. 
No external faults were 
detected. Relay locks upon 
power up and will not release

Replace the MSR42 and retry

Содержание MSR42

Страница 1: ...MSR42 Control Module User Manual...

Страница 2: ...GI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Rockwell Automation sales office describes some important differences between...

Страница 3: ...nd GmbH are available online at www ab com The actual list of relevant safety data and applied standards is given in these documents Introduction The MSR4x is a family of extremely compact safety cont...

Страница 4: ...light curtain Figure 16 Applications Typical applications Typical MSR42 base module applications are Presses Robotic cells with automatic insertion Assembly lines Indexing tables Conveyor systems Auto...

Страница 5: ...ustomer Configurations The configuration of a MSR42 control module is set up via of the USB optical interface and the Allen Bradley GuardShield Software Configuration Diagnostic Tool The configuration...

Страница 6: ...and c All relevant data of the actual configuration are always described in the actual configuration control document for that controller Make sure that the actual document is always stored near to t...

Страница 7: ...SD t em Basic configuration The maximum controller response time t C for the MSR42 control module is given in chapter 14 However depending from the connected Micro 400 light curtain the response time...

Страница 8: ...e of a very short safety light curtain interruption the safety outputs will stay low Relays open for 80ms at minimum A start signal will only be recognized after the 80ms duration EDM or start release...

Страница 9: ...if e g the protective field is interrupted Figure9 ConnectingaSafetyOverridekeyswitchandtheassociatedlamp Depending on the risk evaluation when using a Safety override key operated switch a correspond...

Страница 10: ...wo types of blanking available through the MSR42 Fixed blanking Floating blanking When blanking is activated this has to be clearly indicated by a display or a lamp The MSR42 has only one monitored ou...

Страница 11: ...he double scan mode in the Micro 400 window of the MSR42 Configuration Diagnostic Tool software see Double Scan Filter in Software Configuration Tool Manual Testing the MSR42 standard Blanking area Fi...

Страница 12: ...aults apply to the Out of Box configurations only Reference Table 15 for detailed information Table15 The lock out mode of a MSR42 control module may be reset by one of two methods 1 Power down then P...

Страница 13: ...40R P226AGS NNR Relay Input Voltage Reset Outputs Cat No MSR45E Safety Relay Expansion Module SuppliedbyMSR41 or MSR42 Determined by MSR41 or MSR42 2 N O 440 P4NANS Part number Description 440R ACABL1...

Страница 14: ...y HW Hardware Version SafetyLevel Cat Safetycategory according to EN ISO 13849 1 SafetyLevel SIL Safety integrity level according to EN 61508 SafetyLevel PL Performance level acc to EN ISO 13849 1 Pow...

Страница 15: ...t UN coded Maximum cable length for safety switches 50 m out and back total 100 m See page 6 or 10 Safety Prevention Lamp Minimum current at Lamp 0 9 A with lamp switched on GPIO1 GPIO4 Outputs to saf...

Страница 16: ...ro 400 Evaluation time t EvalLC see label light curtain only important for interrupt ignore time Controller response time t C 14 70 ms Stop delay time t delay 0 00 ms Interrupt ignore time t ignore 0...

Страница 17: ...2004 A1 2008 Safety of machinery Electro sensitive protective equipment Part 1 General requirements and tests IEC 61496 2 2006 Safety of machinery Electro sensitive protective equipment Part 2 Particu...

Страница 18: ...221AGS MSR41 base module 440R P226AGS NNR MSR42 base module 445L 104794 B MSR42 base module customer configuration 440R P4NANS MSR45E expander module 445L 1 MSR45E expander module customer configurati...

Страница 19: ...hi toimuda enne kui installeerija on omandanud koopia tootja instruktsioonidega keeles mida ta ise valdab Instruktsioonid erinvates keeltes on saadaval siin http rockwellautomation com literature SUOM...

Страница 20: ...aan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax...

Отзывы: