Light Curtain Multi-Function Control Module User Manual

Or

i

g

i

nal 

i

nstruct

i

ons

detected and stop the Safety override function from becoming activated. 
After one of the circuits is opened, the amount of time until the safety 
function of a safety component is active again is maximum the response 
time of the MSR42 module.

If an application does not require a safety override lamp (only allowed 
after a safety evaluation corresponding to EN 12100), the monitoring of 
the lamp can be deactivated in the configuration. 

Note that the lamp still will indicate the override function, but is no 
longer monitored. Instead of a safety prevention key switch, an enabling 
switch or two independent, safety position sensors may be used, 
depending on the application and the risk assessment.

Table 8

Table 9

OSSD connect

i

ons

Overall response time of a system is the sum of the response time of the 
OSSD outputs of the connected safety component (e.g. light curtains or 
laser scanners) and the response time of the MSR42 and if used the 
MSR45E modules (see Configuration Control Document).

Figure 10: Connection of up to two OSSD safety components  (e.g. GuardShield Safe4 light 
curtain systems)

Mut

i

ng

Muting is the temporary automatic suspension of a safety function. Using 
the USB/optical interface and the “Configuration & Diagnostic 
Software” different types of muting can be configured. There are several 
muting option settings for light curtain systems. Details about different 
types of muting and their characteristics can be found in the software 
MSR42 Software “Configuration & Diagnostic Tool” and the 
configured muting parameters are listed in the corresponding 
configuration control document.

Blank

i

ng

Blanking is typically used to allow a material to pass through the light 
curtain during normal operation without causing a fault or stop 
condition. This can include a sheet of metal passing through the light 
curtain before an operation is performed to form the material. The Light 
curtain will permit the material at a specific thickness but nothing more 
without causing the safety outputs to turn off.

The MSR42 already supports teach-in fixed blanking via the basic 
configuration.

There are two types of blanking available through the MSR42:

• Fixed  blanking
• Floating  blanking   

When blanking is activated this has to be clearly indicated by a display or 
a lamp. The MSR42 has only one monitored output available for muting 
or blanking lamps. Therefore, muting and blanking cannot be configured 
simultaneously.

On cascaded light curtains check especially for the beams in the area of 
the end of the protective fields. In case of faulty settings the blanking 
range may be unintentionally on the wrong stick.

Fixed blanking with monitoring requires the material to be present at all 
times to prevent a fault condition. In many applications, the material may 
shift slightly during normal operation. This can cause up to one more 
beam to be blocked. Since this can occur during normal operation, the 
MSR42 is configured to permit one additional beam to be blocked 
without causing a fault (beam tolerance: -1 beam). As a result of adding 
one more beam to the configured blanked area, it increases the resolution 
of the light curtain. The table below shows the new resolution.

Table 10

Terminal

LED green

No LED flashing

GPIO3

Contact GPIO1/GPIO3 closed

Contact GPIO1/GPIO3 open

GPIO4

Contact GPIO2/GPIO4 closed

Contact GPIO2/GPIO4 open

Terminal

LED off

LED orange

Lamp

Safety override circuits opened

Safety override circuits closed

1.  The use of the “Safety override” 

function is only allowed in 
applications, for which the risk 
analysis (EN ISO 12100-1 and 
EN14121) permits for the override of a 
safety component. As a general rule, 
emergency stop buttons may never 
be overridden! The safety override key 
for this switch has to be stored 
securely, so that only authorized 
personnel have access to this key. 

2.  The function “Safety override” can not 

be understood as the function 
“Muting” which is specified as the 
temporary automatic suspension of a 
safety function in the standard IEC 
61496-1 A.7 or IEC 62046! Additional 
requirements have to be fulfilled to 
realize the “Muting” function which 
are not described here.

SensaGuard safety switch OSSD outputs 
cannot be connected to the GPIO1-
GPIO4.

After configuring one of the Blanking 
functions, the light curtain resolution may 
be changed. Therefore it is necessary to 
attach an updated label to the Light 
Curtain noting the changed resolution 
has changed.

standard

Blanking area

Finger resolution

14mm

24mm

Hand resolution

30mm

55mm

Содержание MSR42

Страница 1: ...MSR42 Control Module User Manual...

Страница 2: ...GI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Rockwell Automation sales office describes some important differences between...

Страница 3: ...nd GmbH are available online at www ab com The actual list of relevant safety data and applied standards is given in these documents Introduction The MSR4x is a family of extremely compact safety cont...

Страница 4: ...light curtain Figure 16 Applications Typical applications Typical MSR42 base module applications are Presses Robotic cells with automatic insertion Assembly lines Indexing tables Conveyor systems Auto...

Страница 5: ...ustomer Configurations The configuration of a MSR42 control module is set up via of the USB optical interface and the Allen Bradley GuardShield Software Configuration Diagnostic Tool The configuration...

Страница 6: ...and c All relevant data of the actual configuration are always described in the actual configuration control document for that controller Make sure that the actual document is always stored near to t...

Страница 7: ...SD t em Basic configuration The maximum controller response time t C for the MSR42 control module is given in chapter 14 However depending from the connected Micro 400 light curtain the response time...

Страница 8: ...e of a very short safety light curtain interruption the safety outputs will stay low Relays open for 80ms at minimum A start signal will only be recognized after the 80ms duration EDM or start release...

Страница 9: ...if e g the protective field is interrupted Figure9 ConnectingaSafetyOverridekeyswitchandtheassociatedlamp Depending on the risk evaluation when using a Safety override key operated switch a correspond...

Страница 10: ...wo types of blanking available through the MSR42 Fixed blanking Floating blanking When blanking is activated this has to be clearly indicated by a display or a lamp The MSR42 has only one monitored ou...

Страница 11: ...he double scan mode in the Micro 400 window of the MSR42 Configuration Diagnostic Tool software see Double Scan Filter in Software Configuration Tool Manual Testing the MSR42 standard Blanking area Fi...

Страница 12: ...aults apply to the Out of Box configurations only Reference Table 15 for detailed information Table15 The lock out mode of a MSR42 control module may be reset by one of two methods 1 Power down then P...

Страница 13: ...40R P226AGS NNR Relay Input Voltage Reset Outputs Cat No MSR45E Safety Relay Expansion Module SuppliedbyMSR41 or MSR42 Determined by MSR41 or MSR42 2 N O 440 P4NANS Part number Description 440R ACABL1...

Страница 14: ...y HW Hardware Version SafetyLevel Cat Safetycategory according to EN ISO 13849 1 SafetyLevel SIL Safety integrity level according to EN 61508 SafetyLevel PL Performance level acc to EN ISO 13849 1 Pow...

Страница 15: ...t UN coded Maximum cable length for safety switches 50 m out and back total 100 m See page 6 or 10 Safety Prevention Lamp Minimum current at Lamp 0 9 A with lamp switched on GPIO1 GPIO4 Outputs to saf...

Страница 16: ...ro 400 Evaluation time t EvalLC see label light curtain only important for interrupt ignore time Controller response time t C 14 70 ms Stop delay time t delay 0 00 ms Interrupt ignore time t ignore 0...

Страница 17: ...2004 A1 2008 Safety of machinery Electro sensitive protective equipment Part 1 General requirements and tests IEC 61496 2 2006 Safety of machinery Electro sensitive protective equipment Part 2 Particu...

Страница 18: ...221AGS MSR41 base module 440R P226AGS NNR MSR42 base module 445L 104794 B MSR42 base module customer configuration 440R P4NANS MSR45E expander module 445L 1 MSR45E expander module customer configurati...

Страница 19: ...hi toimuda enne kui installeerija on omandanud koopia tootja instruktsioonidega keeles mida ta ise valdab Instruktsioonid erinvates keeltes on saadaval siin http rockwellautomation com literature SUOM...

Страница 20: ...aan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax...

Отзывы: