Publication 1762-UM002A-EN-P - July 2002
Module Data, Status, and Channel Configuration
3-5
To Select
(1)
Make these bit settings
De
cimal
Va
lu
e
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Filter
Frequency
10 Hz
Not U
sed
(2
)
1
1
0
6
60 Hz
0
0
0
0
50 Hz
0
0
1
1
250Hz
0
1
1
3
500 Hz
1
0
0
4
1 kHz
1
0
1
5
Open
Circuit
Upscale
0
0
0
Downscale
0
1
32
Hold Last State
1
0
64
Zero
1
1
96
Tempera-
ture Units
Degrees C
0
0
Degrees F
1
128
Input
Type
Thermocouple
J
0
0
0
0
0
Thermocouple K
0
0
0
1
256
Thermocouple T
0
0
1
0
512
Thermocouple E
0
0
1
1
768
Thermocouple R
0
1
0
0
1024
Thermocouple S
0
1
0
1
1280
Thermocouple B
0
1
1
0
1536
Thermocouple N
0
1
1
1
1792
Thermocouple C
1
0
0
0
2048
-50 to +50 mV
1
0
0
1
2304
-100 to +100 mV
1
0
1
0
2560
Data
Format
Raw/
Proportional
0
0
0
0
Engineering
Units
0
0
1
4096
Engineering
Units X 10
1
0
0
16384
Scaled-for-PID
0
1
0
8192
Percent Range
0
1
1
12288
Enable
Channel
Disable
0
0
Enable
1
-32768
(1) Default values are in bold type and are indicated by zero bit settings. For example, the default filter frequency is 60Hz.
(2) An attempt to write any non-valid (spare) bit configuration into any selection field results in a module configuration error.
Содержание MicroLogix 1200
Страница 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Страница 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Страница 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Страница 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Страница 134: ...Publication 1762 UM002A EN P July 2002 E 8 Module Configuration Using MicroLogix 1200 and RSLogix 500...
Страница 143: ...AB Parts...
Страница 144: ...Publication 1762 UM002A EN P July 2002 5 Copyright 2002 Rockwell Automation All rights reserved Printed in the U S A...