Publication 1762-UM002A-EN-P - July 2002
Installation and Wiring
2-9
•
If it is necessary to connect the shield drain wire at the module
end, connect it to earth ground using a panel or DIN rail
mounting screw.
•
Refer to
Industrial Automation Wiring and Grounding
Guidelines
, Allen-Bradley publication 1770-4.1, for additional
information.
Noise Prevention
•
Route field wiring away from any other wiring and as far as
possible from sources of electrical noise, such as motors,
transformers, contactors, and ac devices. As a general rule, allow
at least 15.2 cm (6 in.) of separation for every 120V of power.
•
Routing field wiring in a grounded conduit can reduce electrical
noise.
•
If field wiring must cross ac or power cables, ensure that they
cross at right angles.
•
To limit the pickup of electrical noise, keep thermocouple and
millivolt signal wires as far as possible from power and load
lines.
•
If noise persists for a device, try grounding the opposite end of
the cable shield. (You can only ground one end at a time.)
Wiring
Terminal Block Layout
Labeling the Terminals
A write-on label is provided with the module. Mark the identification
of each terminal with permanent ink, and slide the label back into the
door.
IN1 -
IN1 +
IN 0 -
IN 0 +
IN2 -
IN2 +
CJC
CJC
IN3 -
IN3 +
Содержание MicroLogix 1200
Страница 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Страница 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Страница 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Страница 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Страница 134: ...Publication 1762 UM002A EN P July 2002 E 8 Module Configuration Using MicroLogix 1200 and RSLogix 500...
Страница 143: ...AB Parts...
Страница 144: ...Publication 1762 UM002A EN P July 2002 5 Copyright 2002 Rockwell Automation All rights reserved Printed in the U S A...