Publication 1762-UM002A-EN-P - July 2002
2-14
Installation and Wiring
Calibration
The thermocouple module is initially calibrated at the factory. The
module also has an autocalibration function.
When an autocalibration cycle takes place, the module’s multiplexer is
set to system ground potential and an A/D reading is taken. The A/D
converter then sets its internal input to the module’s precision voltage
source, and another reading is taken. The A/D converter uses these
numbers to compensate for system offset (zero) and gain (span)
errors.
Autocalibration of a channel occurs whenever a channel is enabled.
You can also program your module to perform cyclic calibration
cycles, every five minutes. See Selecting Enable/Disable Cyclic
Calibration (Word 4, Bit 0) on page 3-14.
To maintain optimal system accuracy, periodically perform an
autocalibration cycle.
IMPORTANT
The module does not convert input data while the
calibration cycle is in progress following a change in
configuration. Module scan times are increased by up
to 112 ms during cyclic autocalibration.
Содержание MicroLogix 1200
Страница 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Страница 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Страница 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Страница 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Страница 134: ...Publication 1762 UM002A EN P July 2002 E 8 Module Configuration Using MicroLogix 1200 and RSLogix 500...
Страница 143: ...AB Parts...
Страница 144: ...Publication 1762 UM002A EN P July 2002 5 Copyright 2002 Rockwell Automation All rights reserved Printed in the U S A...