Publication 1762-UM002A-EN-P - July 2002
2-10
Installation and Wiring
Wiring the Finger-Safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1.
Route the wire under the terminal pressure plate. You can use
the stripped end of the wire or a spade lug. The terminals will
accept a 6.35 mm (0.25 in.) spade lug.
2.
Tighten the terminal screw making sure the pressure plate
secures the wire. Recommended torque when tightening
terminal screws is 0.904 Nm (8 in-lbs).
3.
After wiring is complete, remove the debris shield.
ATTENTION
!
Be careful when stripping wires. Wire fragments
that fall into a module could cause damage when
power is applied. Once wiring is complete, ensure
the module is free of all metal fragments.
TIP
If you need to remove the finger-safe cover,
insert a screw driver into one of the square
wiring holes and gently pry the cover off. If
you wire the terminal block with the
finger-safe cover removed, you will not be
able to put it back on the terminal block
because the wires will be in the way.
Содержание MicroLogix 1200
Страница 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Страница 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Страница 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Страница 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Страница 134: ...Publication 1762 UM002A EN P July 2002 E 8 Module Configuration Using MicroLogix 1200 and RSLogix 500...
Страница 143: ...AB Parts...
Страница 144: ...Publication 1762 UM002A EN P July 2002 5 Copyright 2002 Rockwell Automation All rights reserved Printed in the U S A...